Type 2 AC surge protector - Re-inforced - 1-pole - pluggable

DAC80S-10-150
DAC80S-10-150
Part Number: 821210121
  • Re-inforced Type 2 AC surge protector
  • Single phase
  • In : 40 kA
  • Imax : 80 kA
  • Pluggable module for each phase
  • Remote signaling
  • EN 61643-11, IEC 61643-11 and UL1449 ed.4 compliance

The new DAC80 range is defined by its high Imax parameter of 80 kA. Classified in Type 2, the products of this range are intended to be installed inside the main electrical panel. Its Imax setting of 80 kA makes the DAC80 recommended for installations located in areas susceptible to very strong lightning strikes. Thanks to its very high discharge capacity, this range will have a longer service life than conventional AC surge protection of Type 2 with Imax @ 40 kA. The electrical diagram of the DAC80 series consists of a block of two high-energy varistors combined with a single thermal disconnect system. CITEL is the only manufacturer to offer a complete range of products reaching such a high Imax. The products comply with EN 61643-11, IEC 61643-11 and UL1449 ed.4.


SPD type 2
Max. AC operating voltage Uc 150 Vac
Temporary Over Voltage (TOV) Charasteristics - 5 sec. UT 180 Vac withstand
Temporary Over Voltage (TOV) Charasteristics - 120 mn UT 230 Vac disconnection
Residual Current Ipe < 1 mA
Follow current If None
Nominal discharge current In 40 kA
Max. discharge current Imax 80 kA
Protection level Up 0.9 kV
Residuel voltage at 5 kA Up-5kA 0.7 kV
Admissible short-circuit current Isccr 50 000 A
Technology MOV
SPD configuration 1-pole
Connection to Network By screw terminals: 2.5-25 mm² (35 mm² rigid)
Format Plug-in modular box
Plugable Yes
Mounting Symmetrical rail 35 mm (EN 60715)
Housing material Thermoplastic UL94 V-0
Operating temperature Tu -40/+85°C
Protection rating IP20
Failsafe mode Disconnection from AC network
Disconnection indicator 1 mechanical indicator - Red/Green
Spare module(s) MDAC80-150
Remote signaling of disconnection Output on changeover contact
Max. Voltage/Current for remote signaling 250 V / 0.5 A (AC) / 30 V / 3 A (DC)
Dimensions See diagram - 1TE (EN43880)
Weight 0.121 kg
Standards compliance IEC 61643-11 / EN 61643-11 / UL1449 ed.4
Thermal disconnector Internal
Installation ground fault breaker Type 'S' or delayed
Fuses 50 A mini. - 125 A max. - Fuses Type gG