Contact : +33 1 41 23 50 23 (9:00 – 17:00 CEST)

Type 1+2+3 AC surge protector - 3-phase+N

DS254VG-300
Part Number 3713
DS254VG-300
Availability:
€822.00 (excl. tax)

Available within 3 weeks

  • Type 1+2+3 unipolar surge protector
  • 25 kA on 10/350µs impulse
  • Low voltage Up
  • Internal disconnection, status indicator and remote signaling
  • Optimized to TOV
  • IEC 61643-11 and UL1449 ed.5 compliance

The products of the range DS250VG is an extreme duty Type 1+2+3 AC surge protector device designed to protect at the entrance of the electrical installation. This SPD is particularly useful in a high lightning density area where the risk of heavy surge current or even direct strike is high (eg: buildings equipped with lightning rods). The `Spark gap + Varistor` technology allows a very low level of protection and an absence of following current. The DS250VG is mounted on a DIN Rail and has a double connection for the active conductor, which allows an optimized connection to the network.


SPD type
1+2+3
Network
230/400 V 3-phase+N
AC system
TNS
Nominal line voltage
Un 230/400 Vac
Max. AC operating voltage
Uc 255 Vac
Max. load current
if series connection
IL 100 A
Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
UT 335 Vac withstand
Temporary Over Voltage (TOV) Characteristics - 120 mn
Without disconnection or with safety disconnection
UT 440 Vac withstand
Residual Current
Leakage current to Ground
Ipe None
Follow current
If None
Nominal discharge current
15 x 8/20 µs impulses
In 30 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 70 kA
Impulse current by pole
max. withstand 10/350µs by pole
Iimp 25 kA
Total lightning current
max. total withstand @ 10/350µs
Itotal 100 kA
Withstand on Combination waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
Uoc 20 kV
Withstand on overvoltages IEEE C62.41.1
20 kV
Specific energy by pole
max. withstand 10/350 µs
W/R 156 kJ/ohm
Connection mode(s)
L/PE and N/PE
Protection mode(s)
Common mode
Residual voltage
@ In (8/20 µs)
Up-in 1.1 kV
Protection level N/PE
@ In (8/20µs)
Up N/PE 1.5 kV
Protection level L/PE
@ In (8/20µs)
Up L/PE 1.5 kV
Admissible short-circuit current
Isccr 50 000 A
Technology
VG Technology (MOV+GSG)
SPD configuration
3-phase+Neutral
Connection to Network
By screw terminals: 6-35mm² / by bus
Format
1-pole modular box assembled
Mounting
Symmetrical rail 35 mm (EN 60715)
Housing material
Thermoplastic UL94 V-0
Operating temperature
Tu -40/+85°C
Protection rating
IP20
Failsafe mode
Disconnection from AC network
Disconnection indicator
1 mechanical indicator by pole
Remote signaling of disconnection
Output on changeover contact
Dimensions
See diagram
Weight
0.91 kg
Standards compliance
IEC 61643-11 / EN 61643-11 / UL1449 ed.5
Certification
UL Recognized
Thermal disconnector
Internal
Installation ground fault breaker
Type 'S' or delayed
Back-up protection device
Fuse assembly: SFD1-25-40S / or Fuses Type gG 315 A