Type 1+2 AC surge protector - 1-pole
DS250VG-120
Part Number: 2787
- Type 1+2+3 unipolar surge protector
- 25 kA on 10/350µs impulse
- Low voltage Up
- Internal disconnection, status indicator and remote signaling
- Optimized to TOV
- IEC 61643-11 compliance
- UL1449 ed.4 recognition
The DS250VG is an extreme duty Type 1+2+3 AC surge protector device designed to protect at the entrance of the electrical installation.
This SPD is particularly useful in a high lightning density area where the risk of heavy surge current or even direct strike is high (eg: buildings equipped with lightning rods).
The DS250VG is one-pole SPD and can be used in common mode or common and differential mode.
DS250VG AC surge protectors are designed to be connected in multi-pole configuration to protect single-phase, 3-phase and 3-phase+Neutral AC networks, sometimes associated with a dedicated N/PE SPD.
Select another reference:
SPD type | 1+2+3 | |
Network | 120/208 V | |
Nominal line voltage | Un | 120 Vac |
Max. AC operating voltage | Uc | 150 Vac |
Max. load current | IL | 100 A |
Temporary Over Voltage (TOV) Charasteristics - 5 sec. | UT | 180 Vac withstand |
Temporary Over Voltage (TOV) Charasteristics - 120 mn | UT | 230 Vac withstand |
Residual Current | Ipe | None |
Follow current | If | None |
Nominal discharge current | In | 30 kA |
Max. discharge current | Imax | 70 kA |
Impulse current by pole | Iimp | 25 kA |
Withstand on Combination waveform IEC 61643-11 | Uoc | 20 kV |
Withstand on overvoltages IEEE C62.41.1 | 20 kV | |
Specific energy by pole | W/R | 156 kJ/ohm |
Connection mode(s) | L/N or L/PE | |
Protection mode(s) | Common Mode or Differential Mode | |
Protection level | Up | 1 kV |
Residual voltage | Up-in | 0.7 kV |
Residuel voltage at 5 kA | Up-5kA | 0.4 kV |
Admissible short-circuit current | Isccr | 50 000 A |
Technology | VG Technology (MOV+ GSG) | |
SPD configuration | 2 poles | |
Connection to Network | By screw terminals : 6-35 mm² / by bus | |
Format | 1-pole modular box | |
Mounting | Symmetrical rail 35 mm (DIN 60715) | |
Housing material | Thermoplastic UL94 V-0 | |
Operating temperature | Tu | -40/+85°C |
Protection rating | IP20 | |
Failsafe mode | Disconnection | |
Disconnection indicator | 1 mechanical indicator | |
Remote signaling of disconnection | Output on changeover contact | |
Dimensions | See diagram |
Standards compliance | IEC 61643-11 / EN 61643-11 / UL1449 4ed. | |
Certification | UL / EAC |
Thermal disconnector | Internal | |
Installation ground fault breaker | Type 'S' or delayed | |
Fuses | Fuses type gG - 315 A |