Contact : +33 1 41 23 50 23 (9:00 – 17:00 CEST)

1-pair DIN rail plug-in Data surge protector

DLA-24D3/R
Part Number 6401034
DLA-24D3/R
  • High current data transmission
  • Common mode and differential mode protection
  • Data lines, including those isolated from Earth
  • Compact DIN rail enclosure, high density protection
  • Protection of shield wire
  • Plug-out with line cut-off
  • Location and test categories: D1, C2, C3
  • IEC 61643-21 compliance

DLA surge protectors are designed to protect, against surge voltages due to lightning, terminals equipment connected to industrial buses, telecom lines or datalines. These surge protectors must be installed on symmetrical DIN rail and are available for most of the transmission lines: line voltage from 6 to 170V, bitrate up to 10 Mbit/s. D3 types aim to realize fine protection and D2 types is specific for floating application. These products are 1-pair surge protectors with removable module for easy maintenance.


Network
4-20 mA
Nominal line voltage
Un 24 V
Max. DC operating voltage
Uc 28 Vdc
Max. frequency
f max. > 3 MHz
Insertion loss
< 1 dB
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 20 kA
Line inductance
No
Protection level
@ In (8/20 µs)
Up L/L 40 V
Max. capacitance
C < 50 pF
Impulse current
2 x 10/350µs Test - D1 Category
Iimp 5 kA
Nominal discharge current
C2 Category
In 5 kA
Max. Load current
IL 300 mA
Line resistance
< 4.7 Ohm
Network type
Data Communication
Technology
GDT+Clamping diode
SPD configuration
1-pair+shielded
Connection to Network
Spring terminal: cross section 0.5-2.5mm²
Mounting
Symmetrical rail 35 mm (EN 60715)
Housing material
Thermoplastic UL94 V-0
Operating and storage temperature
-40/+85°C
Protection rating
IP20
Failsafe mode
Short-circuit
Disconnection indicator
Transmission interrupt - default mode 2
Spare module(s)
DLAM-24D3
Dimensions
See diagram
Standards compliance
IEC 61643-21 / EN 61643-21