Contact : +33 1 41 23 50 23 (9:00 – 17:00 CEST)

Type 1+2+3 AC surge protector - 3-phase+N

ZPAC1-13VG-31-275
Part Number 64004
ZPAC1-13VG-31-275
  • Type 1+2+3 AC Surge protection
  • VG Technology
  • For 40 mm busbar systems
  • Iimp 8 kA (10/350 μs)
  • Reduces energy costs: Does not produce flow current and leakage current
  • Certified IEC 61643-11 and EN 61643-11

The ZPAC1 range is a type 1 + 2 + 3 pluggable surge protector for 230/400 3-phase AC network, intended to be integrated into electrical panels equipped with standard 40mm busbars. The solution is available in two impulse current (Iimp) of 12.5 kA or 8kA. Compact, economical and ultra fast implementation, it is intended for business/household buildings equipped with lightning rod. Equipped with exclusive CITEL’s VG technology, the range achieves an high protection level, guaranteeing a maximum protection efficiency, a absence of follow and leakage currents, a simplification of use (no additional lightning arrester required) and a maximum lifetime. The pluggable configuration (quick and easy maintenance) and VG technology (maximum protection efficiency) used by ZPAC1 make it the most relevant choice for electrical contractors and users.


SPD type
IEC 1+2+3
Network
230/400 V 3-phase+N
AC system
TT-TNS
Nominal line voltage
Un 230/400 Vac
Max. AC operating voltage
Uc 275 Vac
Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
UT 335 Vac withstand
Temporary Over Voltage (TOV) Characteristics - 120 mn
Without disconnection or with safety disconnection
UT 440 Vac withstand
Temporary Over Voltage N/PE (TOV HT)
Without disconnection or with safety disconnection
UT 1200 V/300A/200 ms withstand
Residual Current
Leakage current to Ground
Ipe None
Operating current
Continious current at Uc
Ic None
Follow current
If None
Nominal discharge current
15 x 8/20 µs impulses
In 20 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 50 kA
Impulse current by pole
max. withstand 10/350µs by pole
Iimp 12.5 kA
Total lightning current
max. total withstand @ 10/350µs
Itotal 50 kA
Withstand on Combination waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
Uoc 6 kV
Withstand on overvoltages IEEE C62.41.1
20 kV
Specific energy by pole
max. withstand 10/350 µs
W/R 40 kJ/ohm
Connection mode(s)
L/N and N/PE
Protection mode(s)
Common/Differential mode
Protection level L/N
@ In (8/20µs)
Up L/N 1.5 kV
Protection level L/PE
@ In (8/20µs)
Up L/PE 1.5 kV
Residual voltage L/N at 5 kA
@ 5 kA (8/20µs)
Up-5kA 0.7 kV
Admissible short-circuit current
Isccr 50 000 A
Technology
VG Technology (MOV+GSG)
SPD configuration
3-phase+Neutral
Connection to Network
By 40mm busbar and wire for PE: 6-35mm² (50mm²)
Format
Plug-in modular box
Mounting
40 mm busbar systems
Housing material
Thermoplastic UL94 V-0
Operating temperature
Tu -40/+85°C
Protection rating
IP20
Outdoor application
No
Failsafe mode
Disconnection from AC network
Disconnection indicator
1 mechanical indicator by pole
Spare module(s)
ZMDAC1-13VG-275
Remote signaling of disconnection
none
Dimensions
See diagram
Weight
0.7401 kg
Standards compliance
IEC 61643-11 / EN 61643-11 / UL1449 4ed.
Certification
KEMA
Thermal disconnector
Internal
Installation ground fault breaker
Type 'S' or delayed
Back-up protection device
max. 315 A (gL/gG)