  • Compact single-phase Type 2 (or 3) surge protector
  • In : 5 kA
  • Imax : 15 kA
  • Commun/Differential mode
  • Monobloc module
  • Remote signaling
  • EN 61643-11, IEC 61643-11 and UL1449 ed.5 compliance


Select another reference:

SPD type 2 (or 3)
Network 120/208 V
AC system TT-TN
Max. AC operating voltage Uc 150 Vac
Temporary Over Voltage (TOV) Charasteristics - 5 sec. UT 180 Vac withstand
Temporary Over Voltage (TOV) Charasteristics - 120 mn UT 230 Vac disconnection
Temporary Over Voltage N/PE (TOV HT) UT 1200 V/300A/200 ms withstand
Residual Current Ipe None
Follow current If None
Nominal discharge current In 5 kA
Max. discharge current Imax 15 kA
Withstand on Combination waveform IEC 61643-11 Uoc 10 kV
Protection mode(s) L/N and N/PE
Protection level L/N Up L/N 0.7 kV
Protection level N/PE Up N/PE 1.5 kV
Admissible short-circuit current Isccr 10 000 A
Technology MOV+GDT
SPD configuration Single phase
Connection to Network By screw terminals: 1.5-10mm²
Compact Yes
Format Monobloc modular box
Plugable No
Mounting Symmetrical rail 35 mm (EN 60715)
Housing material Thermoplastic UL94 V-0
Operating temperature Tu -40/+85°C
Protection rating IP20
Failsafe mode Disconnection from AC network
Disconnection indicator Green LED OFF
Remote signaling of disconnection output on changeover contact
Wiring for remote signaling 1.5 mm² max.
Max. Voltage/Current for remote signaling 250 V / 0.5 A (AC) / 30 V / 3 A (DC)
Dimensions See diagram - 1TE (EN43880)
Weight 0.093 kg
Standards compliance IEC 61643-11 / EN 61643-11 / UL1449 ed.5
Thermal disconnector Internal
Installation ground fault breaker Type 'S' or delayed
Fuses 20 A min. - 125 A max. - Fuses type gG