Contact : +33 1 41 23 50 23 (9:00 – 17:00 CEST)

1-pair DIN rail plug-in Data surge protector

DLAW-24D3
Part Number 640803
DLAW-24D3
  • Din rail plug-in surge protector
  • 1-pair
  • Un: 24 V
  • Shield wire protection
  • Plug-out with line cut-off
  • IEC 61643-21 compliance
  • UL497A

DLA surge protectors are designed to protect, against surge voltages due to lightning, terminals equipment connected to industrial buses, telecom lines or datalines. These surge protectors must be installed on symmetrical DIN rail and are available for most of the transmission lines: line voltage from 6 to 170V, bitrate up to 10 Mbit/s. D3 types aim to realize fine protection and D2 types is specific for floating application. These products are 1-pair surge protectors with removable module for easy maintenance.

Select another reference:

Network
4-20 mA
Nominal line voltage
Un 24 V
Max. DC operating voltage
Uc 28 Vdc
Max. frequency
f max. > 3 MHz
Insertion loss
< 1 dB
Max. load current
@25°C
IL 300 mA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 20 kA
Line inductance (± 10 %)
non
Protection level
@ In (8/20 µs)
Up L/L 40 V
Impulse current
2 x 10/350µs Test - D1 Category
Iimp 5 kA
Line/Line Nominal discharge current
C2 Category
In L/L 5 kA
Nominal Discharge Current, X-C (Line/Earth)
8/20µs Test x 10 - C2 Category
In L/PE 5 kA
Line resistance (± 10%)
4.7 Ohm
Network type
Data Communication
Disconnection
Specific version with line cut-off in case of removal plug-in module
Technology
GDT+Clamping diode
SPD configuration
1-pair+shielded
Connection to Network
By screw terminal: cross section 0.5-2.5mm²
Format
Plug-in DIN box
Mounting
Symmetrical rail 35 mm (EN 60715)
Housing material
Thermoplastic UL94 V-0
Operating temperature
Tu -40/+85°C
Protection rating
IP20
Failsafe mode
Short-circuit
With line cut-off in case of removal plug-in module
Yes
Disconnection indicator
Transmission interrupt - default mode 2
Spare module(s)
DLAM-24D3
Dimensions
See diagram
Standards compliance
IEC 61643-21 / EN 61643-21 / UL497A