Contact : +33 1 41 23 50 23 (9:00 – 17:00 CEST)

Protection of video surveillance systems against overvoltages



Select another reference:

SPD type
IEC 2+3
Network
Signal video
Network
1 pair signal 0-5 V
Network
24 Vac/Vdc
Nominal line voltage
Un 24 Vac/Vdc
Max. DC operating voltage
Uc 8 Vdc
Max. DC operating voltage
Uc 6 Vdc
Max. DC operating voltage
Uc 30 Vac/Vdc
Max. frequency
f max. 100 Mhz
Max. frequency
f max. 16 MHz
Insertion loss
< 1dB
Insertion loss
< 1dB
Insertion loss
< 0.1 dB
Max. load current @25°C
IL 5 A
Max. load current @25°C
IL 300 mA
Operating current
Continious current at Uc
Ic None
Nominal discharge current
15 x 8/20 µs impulses
In 5 kA
Nominal discharge current
15 x 8/20 µs impulses
In 5 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 10 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 10 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 5 kA
Withstand on Combination waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
Uoc 10 kV / 5 kA
Protection mode(s)
Common/Differential mode
Protection level
@ In (8/20µs)
Up 0.22 kV
Protection level
@ In (8/20µs)
Up 20 V
Protection level
@ In (8/20µs)
Up 20 V
Protection Level
C3 (10/1000μs), 300 applications@10 A, X-X (Line/Line)
Up 20 V
Protection level
C3 (10/1000μs), 300 applications@10 A, X-C (Line/Earth)
Up 20 V
Protection level L/N
@ In (8/20µs)
Up L/N 0.22 kV
Protection level L/PE
@ In (8/20µs)
Up L/PE 0.22 kV
Nominal discharge current
C2 Category
In 2.5 kA
Nominal discharge current
C2 Category
In 2.5 kA
Technology
MOV+GDT
Connection to Network
By screw terminals: 2.5mm² max.
Format
DIN rail or flange
Mounting
DIN rail or plate (flange)
Housing material
Anodized aluminum
Operating temperature
Tu -40/+85°C
Protection rating
IP20
Failsafe mode
Disconnection and Power cut off
Disconnection indicator
Green LED OFF and line cut off
Operating indicator
Green led(s) on
Dimensions
See diagram
Weight
0.184 kg
Standards compliance
IEC 61643-11 / EN 61643-11 / UL1449 ed.5
Thermal disconnector
Internal