Contact : +33 1 41 23 50 23 (9:00 – 17:00 CEST)

Protection of video surveillance systems against overvoltages



Select another reference:

SPD type
IEC 2+3
Network
230 V single-phase
Max. DC operating voltage
Uc 255 Vdc
Max. frequency
f max. 100 Mhz
Insertion loss
< 0.1 dB
Max. load current @25°C
IL 5 A
Operating current
Continious current at Uc
Ic None
Nominal discharge current
15 x 8/20 µs impulses
In 5 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 10 kA
Withstand on Combination waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
Uoc 10 kV / 5 kA
Protection mode(s)
Common/Differential mode
Protection level
@ In (8/20µs)
Up 1.2 kV
Protection Level
C3 (10/1000μs), 300 applications@10 A, X-X (Line/Line)
Up 1.2 kV
Protection level
C3 (10/1000μs), 300 applications@10 A, X-C (Line/Earth)
Up 1.2 kV
Nominal discharge current
C2 Category
In 2.5 kA
Network type
POE Network
Technology
MOV+GDT
Connection to Network
By screw terminals: 2.5mm² max.
Format
DIN rail or flange
Mounting
DIN rail or plate (flange)
Housing material
Anodized aluminum
Operating temperature
Tu -40/+85°C
Protection rating
IP20
Failsafe mode
Disconnection and Power cut off
Disconnection indicator
Green LED OFF and line cut off
Operating indicator
Green led(s) on
Dimensions
See diagram
Weight
0.163 kg
Standards compliance
IEC 61643-21 / EN 61643-21
Thermal disconnector
Internal