Contact : +33 1 41 23 50 23 (9:00 – 17:00 CEST)

Surge protector for Video survey

MSP-VM12/R
Part Number 420413
  • Security camera surge protector
  • AC + Cat.5 (connector RJ45)
  • Compact aluminium housing
  • Rail DIN mounting or plate

MSP-VMxx-R surge protectors were designed to protect video surveillance systems against transient overvoltages generated by lightning or industrial environment. These devices protect, in a single compact housing, all the lines connected to the system: power supply (230Vac, 24Vdc, 12Vdc or 120 Vac), dataline (6 or 8 Vdc). This compact configuration allows a fast installation in a small footprint.


SPD type
IEC 2+3
Network
12 Vac/Vdc
Network
4 pairs Ethernet 100 Base-TX
Nominal line voltage
Un 12 Vac/Vdc
Max. DC operating voltage
Uc 15 Vac/Vdc
Max. DC operating voltage
Uc 8 Vdc
Max. frequency
f max. 125 MHz
Insertion loss
< 1 dB
Insertion loss
< 1dB
Max. load current @25°C
IL 5 A
Max. load current @25°C
IL 300 mA
Operating current
Continious current at Uc
Ic None
Nominal discharge current
15 x 8/20 µs impulses
In 5 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 10 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 5 kA
Withstand on Combination waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
Uoc 10 kV / 5 kA
Protection mode(s)
Common/Differential mode
Protection level
@ In (8/20µs)
Up 20 V
Protection level
@ In (8/20µs)
Up 20 V
Protection Level
C3 (10/1000μs), 300 applications@10 A, X-X (Line/Line)
Up 220 V
Protection level
C3 (10/1000μs), 300 applications@10 A, X-C (Line/Earth)
Up 220 V
Protection level L/N
@ In (8/20µs)
Up L/N 20 V
Protection level L/N
@ In (8/20µs)
Up L/N 20 V
Protection level L/PE
@ In (8/20µs)
Up L/PE 20 V
Protection level L/PE
@ In (8/20µs)
Up L/PE 20 V
Nominal discharge current
C2 Category
In 2.5 kA
Nominal discharge current
C2 Category
In 2.5 kA
Network type
POE Network
Technology
MOV+GDT
Connection to Network
By screw terminals: 2.5mm² max.
Format
DIN rail or flange
Mounting
DIN rail or plate (flange)
Housing material
Anodized aluminum
Operating temperature
Tu -40/+85°C
Protection rating
IP20
Failsafe mode
Disconnection and Power cut off
Disconnection indicator
Green LED OFF and line cut off
Operating indicator
Green Led ON
Dimensions
See diagram
Standards compliance
IEC 61643-11 / EN 61643-11 / UL1449 ed.5
Thermal disconnector
Internal