Contact : +33 1 41 23 50 23 (9:00 – 17:00 CEST)

Outdoor 10 Gigabit POE++ Surge Protective Device - Metallic housing and cable glands

LAN-10G-POE-CR
Part Number 581547
LAN-10G-POE-CR
  • POE++ Compatible (IEEE 802.3bt)
  • 10Gb (5-100m) with Cat6A S/FTP cabling
  • Shielded RJ45 connectors
  • Outdoor applications, IP67 (NEMA 6)
  • Metallic enclosure
  • Conforms to IEC/EN 61643-21
  • SPD categories D1, C3, C2, C1



Network
10Gb/s on Cat6A S/FTP cabling
Protection modes (network)
CM / DM
Protection modes (POE)
CM / DM (common mode / differential mode)
Transmission standard
IEEE 802.3bt
Lightning Protection Zones (LPZ)
0 - 3
Max. DC operating voltage
Uc 3.3 Vdc
Max. operating voltage (POE)
Uc 60 Vdc
Max. frequency, in the channel
f max. 500 MHz
Max. data rate
10 Gbps
Max. load current @25°C
IL 2 A
Max. POE power (4PPOE)
90 W
Max. discharge current
max. withstand @ 8/20 µs, X-C (Line/Earth)
Imax 2 kA
Max. discharge current
max. withstand @ 8/20 µs, 8X-C (1&2+3&6+4&5+7&8 to Earth)
Imax Total 16 kA
Protection Level
C3 (10/1000μs), 300 applications@10 A, X-X (Line/Line)
Up < 10 V
Protection level
C3 (10/1000μs), 300 applications@10 A, X-C (Line/Earth)
Up < 700 V
Protection Level
C3 (10/1000µs), 300 applications @ 10A, (Pair-Pair, POE)
Up < 80 V
Protection Level
C2 (1.2/50µs & 8/20µs), 10 applications, X-C (Line-Earth)
Up < 1000 V
Protection Level
C1 (1.2/50µs & 8/20µs), 300 applications, (Pair-Pair, POE)
Up < 98 V
Impulse current
D1 (10/350μs), 2 applications, X-C (Line/Earth)
Iimp 500 A
Nominal discharge current
C1 (1.2/50us / 8/20µs), 300 applications X-X (Line/Line)
In 300V / 150A
Nominal discharge current
C1 (1.2/50us / 8/20µs), 300 applications, X-C (Pair-Pair, POE)
In 300V / 150A
Nominal discharge current
C2 (1.2/50us / 8/20µs), 10 applications X-C (Line/Earth)
In 4 kV / 2 kA
Line resistance (± 10%)
~ 0 ohms
Capacitance
@1MHz, X-C (Line/Earth)
C < 5 pF
Technology
GDT+TVS diode
SPD configuration
8 wires+shielded
Connection to Network
RJ45 shielded connectors input/output
Cable glands
Metallic/Rubber
Format
Metallic box with connectors input/output
Mounting
Wall / Pole / Plate
Accessory(s) provided
U' bracket
Operating temperature
Tu -40/+85°C
Ingress Protection rating
IP67 (NEMA 6)
Outdoor application
Yes
Failsafe mode
Transmission cut-off - Fault mode 2 (short-circuit)
Pinout
(1-2)(3-6)(4-5)(7-8)
Dimensions
See diagram
Weight
0.65 kg / 1.44 lbs
Standards compliance
IEC 61643-21 / EN 61643-21 / UL497B / IEEE 802.3af/3at/3bt, ANSI/TIA-568-c.1