Compact 1-phase Type 2 (or 3) surge protector - 230 V -Pluggable

DAC15CS-11-320
DAC15CS-11-320
Part Number: 821620321
  • Compact single-phase Type 2 (or 3) surge protector
  • In : 5 kA
  • Imax : 15 kA
  • Commun/Differential mode
  • Pluggable module
  • Remote signaling
  • EN 61643-11, IEC 61643-11 certified
  • UL1449 ed.4 compliance

The DAC15C Type 2 or Type 3 Compact plugable surge protectors (SPD) are intended to be connected at the TGBT or divisional panel level. Their compact format allows them to be installed in very small spaces. The DAC15C SPDs are available have a discharge capacity of 15 kA, in single-phase or 3-phase configuration and with various voltages in order to protect any type of networks. Based on varistance technology equipped with disconnector and associated indicator, these SPD ensure maximum protection efficiency, flow capacity and reliability.


SPD type 2 (or 3)
Network 230/400 V
AC system TT-TN
Max. AC operating voltage Uc 320 Vac
Temporary Over Voltage (TOV) Charasteristics - 5 sec. UT 335 Vac withstand
Temporary Over Voltage (TOV) Charasteristics - 120 mn UT 440 Vac disconnection
Temporary Over Voltage N/PE (TOV HT) UT 1200 V/300A/200 ms withstand
Residual Current Ipe None
Follow current If None
Nominal discharge current In 5 kA
Max. discharge current Imax 15 kA
Total Maximum discharge current Imax Total 30 kA
Withstand on Combination waveform IEC 61643-11 Uoc 10 kV
Protection mode(s) L/PE and N/PE
Protection level N/PE Up N/PE 1.5 kV
Protection level Up L/N 1.1 kV
Admissible short-circuit current Isccr 10 000 A
Technology MOV+GDT
SPD configuration Single phase
Connection to Network by screw terminals: L/N = 1.5-10mm² (16mm² rigid) or PE = 2.5-25mm² (35 mm² rigid)
Format Plug-in modular box
Plugable Yes
Mounting Symmetrical rail 35 mm (EN 60715)
Housing material Thermoplastic UL94 V-0
Operating temperature Tu -40/+85°C
Protection rating IP20
Failsafe mode Disconnection from AC network
Disconnection indicator 1 mechanical indicator - Red/Green
Spare module(s) MDAC15C-11-320
Remote signaling of disconnection Output on changeover contact
Wiring for remote signaling 1.5 mm² max.
Max. Voltage/Current for remote signaling 250 V / 0.5 A (AC) / 30 V / 3 A (DC)
Dimensions See diagram - 1TE (EN43880)
Standards compliance IEC 61643-11 / EN 61643-11 / UL1449 ed.4
Certification KEMA / EAC
Thermal disconnector Internal
Installation ground fault breaker Type 'S' or delayed
Fuses 20 A min. - 125 A max. - Type gG