Type 2 AC surge protector - 3-phase
DS43-400
Part Number: 461403
- Type 2 AC Multipolar surge protector
- In : 20 kA
- Imax total : 120 kA
- Pluggable module for each phase
- Remote signaling option
- NF EN 61643-11, CEI 61643-11 compliance
- UL1449 ed.15

used mainly for primary protection of single and 3- phase networks at the main electrical panel. They provide common-mode or common and differential mode. This SPD is based on high energy varistor equipped with thermal disconnector and failure indicator, to comply with standards.
The DS40 surge protectors are designed to be used in a multipolar configuration to protect single-phase, 3-phase or 3-phase+Neutral AC networks.They are sometimes associated with dedicated N/PE surge protector based on gas tube technology.
Select another reference:
- DS41-1000
- DS41-120
- DS41-230
- DS41-280
- DS41-320
- DS41-385
- DS41-400
- DS41-600
- DS41-690
- DS42-120
- DS42-120/G
- DS42-230
- DS42-230/G
- DS42-280
- DS42-280/G
- DS42-320
- DS42-320/G
- DS42-385/G
- DS42-400
- DS43-120
- DS43-230
- DS43-280
- DS43-320
- DS43-385
- DS43-400
- DS43-480
- DS44-120
- DS44-120/G
- DS44-230
- DS44-230/G
- DS44-230/G/DE
- DS44-280
- DS44-280/G
- DS44-320
- DS44-320/G
- DS44-385
- DS44-385/G
- DS44-400
- DS44-480
SPD type following IEC test |
2 |
Network |
230/400 V 3-phase |
AC system |
IT |
Nominal line voltage |
400 Vac |
Max. AC operating voltage L-N |
440 Vac |
Temporary Over Voltage (TOV) Charasteristics - 5 sec. without disconnection |
580 Vac withstand |
Temporary Over Voltage (TOV) Charasteristics - 120 mn without disconnection or with safety disconnection |
770 Vac disconnection |
Residual Current Leakage current to Ground |
< 1.5 mA |
Operating current Continious current at Uc |
0.5 mA |
Follow current |
None |
Nominal discharge current 15 x 8/20 µs impulses |
20 kA |
Max. discharge current max. withstand @ 8/20 µs by pole |
40 kA |
Total Maximal discharge current max. total withstand @ 8/20 µs |
120 kA |
Admissible short-circuit current |
25000 A |
Connection mode(s) |
L/PE |
Protection mode(s) |
Common mode |
Protection level L/PE @ In (8/20µs) |
1.8 kV |
Residual voltage at 10 kA @ 8/20µs |
1.5 kV |
Residuel voltage at 5 kA @ 5 kA (8/20µs) |
1.3 kV |
Technology | MOV |
SPD configuration | 3-phase |
Connection to Network | By screw terminals: 2.5-25 mm² / by bus |
Format |
Plug-in modular box |
Mounting |
Symmetrical rail 35 mm (EN60715) |
Housing material | Thermoplastic UL94-V0 |
Operating temperature | -40/+85°C |
Protection rating | IP20 |
Failsafe behavior | Disconnection |
Disconnection indicator | 1 mechanical indicator by pole |
Spare module(s) |
DSM40-400 |
Remote signaling of disconnection |
option DS43S-400 : output on changeover contact |
Dimensions |
See diagram |
Certification |
UL / CSA /EAC |
Standards compliance |
IEC 61643-11 / EN 61643-11 / UL1449 4ed. |
Thermal disconnector | Internal |
Fuses |
Fuses type gG - 50 A |
Installation ground fault breaker | Type 'S' or delayed |