Type 2 AC surge protector - 3-phase
DAC50-30-440
Part Number: 821110413
- Type 2 AC surge protector
- In : 20 kA
- Imax : 50 kA
- Pluggable module for each phase
- Remote signaling option
- NF EN 61643-11, IEC 61643-11 compliance
The pluggable surge protectors Type 2 DAC50, are designed to protect AC powerline at the main switchboard of the installation.
These SPDs are based on high energy varistor equipped with thermal disconnector and failure indicator, to comply with standards and to provide a maximum protection efficiency, an high impulse current capability and a improved reliability.
The surge protectors DAC50 are available in multipolar version and in several voltages to protect single or 3-phase networks.
Select another reference:
- DAC50-10-150
- DAC50-10-275
- DAC50-10-320
- DAC50-10-530
- DAC50-10-660
- DAC50-10-760
- DAC50-11-150
- DAC50-11-275
- DAC50-11-320
- DAC50-20-150
- DAC50-20-275
- DAC50-20-320
- DAC50-20-440
- DAC50-20-530
- DAC50-30-150
- DAC50-30-275
- DAC50-30-320
- DAC50-30-440
- DAC50-30-530
- DAC50-30-660
- DAC50-31-150
- DAC50-31-275
- DAC50-31-320
- DAC50-40-150
- DAC50-40-275
- DAC50-40-320
- DAC50-40-440
- DAC50-40-530
SPD type | 2 | |
Network | 230/400 V 3-phase | |
AC system | IT | |
Max. AC operating voltage L-N | Uc | 440 Vac |
Temporary Over Voltage (TOV) Charasteristics - 5 sec. | UT | 580 Vac withstand |
Temporary Over Voltage (TOV) Charasteristics - 120 mn | UT | 770 Vac disconnection |
Residual Current | Ipe | < 1 mA |
Follow current | If | None |
Nominal discharge current | In | 20 kA |
Max. discharge current | Imax | 50 kA |
Total Maximum discharge current | Imax Total | 150 kA |
Protection mode(s) | L/PE | |
Protection level L/PE | Up L/PE | 2 kV |
Residual voltage L/PE at 5 kA | Up-5kA | 1.5 kV |
Admissible short-circuit current | Isccr | 50 000 A |
Technology | MOV | |
SPD configuration | 3-phase | |
Connection to Network | By screw terminals: 2.5-25 mm² (35 mm² rigid) | |
Format | Plug-in modular box | |
Mounting | Symmetrical rail 35 mm (DIN 60715) | |
Housing material | Thermoplastic UL94 V-0 | |
Operating temperature | Tu | -40/+85°C |
Protection rating | IP20 | |
Failsafe mode | Disconnection from AC network | |
Disconnection indicator | 1 mechanical indicator by pole - Red/Green | |
Spare module(s) | MDAC50-440 | |
Remote signaling of disconnection | option DAC50S-30-440 : output on changeover contact | |
Dimensions | See diagram - 3 TE (EN43880) | |
Weight | 0.316 kg |
Standards compliance | IEC 61643-11 / EN 61643-11 / UL1449 4ed. | |
Certification | OVE / UL / EAC |
Thermal disconnector | Internal | |
Installation ground fault breaker | Type 'S' or delayed | |
Fuses | 50 A mini. - 125 A max. - Fuses Type gG |