Contact : +33 1 41 23 50 23 (9:00 – 17:00 CEST)

Type 2 AC surge protector - 1-pole - pluggable

DACF25-10-320
Part Number 821410311
DACF25-10-320
  • Type 2 AC surge protector
  • In : 15 kA
  • Imax : 25 kA
  • Internal Fuse
  • Pluggable module for each phase
  • Remote signaling option
  • NF EN 61643-11, IEC 61643-11, UL1449 ed.5 compliance

Type 2 DACF25 SPDs are used mainly for primary surge protection of single and 3-phase AC networks at the main switchboard. In addition to their thermal disconnector, the range is equipped with an internal fuse against short-circuit currents, which avoids the use of an external fuse or circuit-breaker as requested by standard. The operation of one of the both disconnectors will activate the indicator and the remote signalling (option). This compact solution simplifies the implementation and minimum space. The DACF25 surge protectors are designed to be used in a multipolar configuration to protect single-phase, 3-phase.

Select another reference:

SPD type
2
Max. AC operating voltage
Uc 320 Vac
Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
UT 335 Vac withstand
Temporary Over Voltage (TOV) Characteristics - 120 mn
Without disconnection or with safety disconnection
UT 440 Vac disconnection
Residual Current
Leakage current to Ground
Ipe < 1 mA
Follow current
If None
Nominal discharge current
15 x 8/20 µs impulses
In 15 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 25 kA
Protection level
@ In (8/20µs)
Up 1.5 kV
Residual voltage at 5 kA
@ 5 kA (8/20µs)
Up-5kA 1.2 kV
Admissible short-circuit current
Isccr 100 000 A
Technology
MOV
SPD configuration
Single phase
Connection to Network
By screw terminals: 2.5-25mm² (35mm² rigid)
Format
Plug-in modular box
Plugable
Yes
Mounting
Symmetrical rail 35 mm (EN 60715)
Housing material
Thermoplastic UL94 V-0
Operating temperature
Tu -40/+85°C
Protection rating
IP20
Failsafe mode
Disconnection from AC network
Disconnection indicator
1 mechanical indicator - Red/Green
Spare module(s)
MDACF25-320
Remote signaling of disconnection
option DACF25S-10-320 : output on changeover contact
Wiring for remote signaling
1.5 mm² max.
Max. Voltage/Current for remote signaling
250 V / 0.5 A (AC) / 30 V / 3 A (DC)
Dimensions
See diagram - 1TE (EN43880)
Standards compliance
IEC 61643-11 / EN 61643-11 / UL1449 ed.5
Thermal disconnector
Internal
Installation ground fault breaker
Type 'S' or delayed
Back-up protection device
internal (equivalent AC rating : 40 A, gG Type)
Integrated fuses
Yes