Type 2 AC surge protector - 1-pole - pluggable
DACF25-10-275
DACF25-10-275
Part Number: 821410211
  • Type 2 AC surge protector
  • In : 15 kA
  • Imax : 25 kA
  • Interne Disconnection device
  • Pluggable module for each phase
  • Remote signaling option
  • NF EN 61643-11, CEI 61643-11 compliance
  • UL1449 ed.4
CITEL_Certif_CB_DACF-xx-275.pdf Installation Sheet

Type 2 DACF25 SPDs are used mainly for primary surge protection of single and 3-phase AC networks at the main switchboard. In addition to their thermal disconnector, the range is equipped with a internal fuse against short-circuit currents, which avoidsthe use of a external fuse or circuit-breaker as requested by standard. The operation of one of the both disconnectors will activate the indicator and the remote signalling (option). This compact solution simplifies the implementation and minimum space. The DACF25 surge protectors are designed to be used in a multipolar configuration to protect single-phase, 3-phase.


SPD type 2
Max. AC operating voltage L-N Uc 275 Vac
Temporary Over Voltage (TOV) Charasteristics - 5 sec. UT 335 Vac withstand
Temporary Over Voltage (TOV) Charasteristics - 120 mn UT 440 Vac disconnection
Residual Current Ipe < 1 mA
Follow current If None
Nominal discharge current In 15 kA
Max. discharge current Imax 25 kA
Protection level Up 1.25 kV
Residuel voltage at 5 kA Up-5kA 1 kV
Admissible short-circuit current Isccr 100 000 A
Technology MOV
SPD configuration 1-pole
Connection to Network By screw terminals: 2.5-25 mm² (35 mm² rigid)
Format Plug-in modular box
Mounting Symmetrical rail 35 mm (DIN 60715)
Housing material Thermoplastic UL94-V0
Operating temperature -40/+85°C
Protection rating IP20
Failsafe mode Disconnection from AC network
Disconnection indicator 1 mechanical indicator - Red/Green
Spare module(s) MDACF25-275
Remote signaling of disconnection option DACF25S-10-275 : output on changeover contact
Wiring for remote signaling 1.5 mm² max.
Maw. Voltage/Current for remote signaling 250 V / 0.5 A (AC) / 30 V / 3 A (DC)
Dimensions See diagram - 1TE (EN43880)
Standards compliance IEC 61643-11 / EN 61643-11 / UL1449 4ed.
Thermal disconnector Internal
Installation ground fault breaker Type 'S' or delayed
Fuses Integrated Fuse