4-pair Telecom surge protector unit
Part Number: 72746
B480-T
- 4-pair surge protection unit
- For Telephone lines
- Removable protection circuit
- Wall mounting and screw connection
- UL497 A&B
|
Network
|
RTC, ADSL, SDSL, SHDSL |
|
|
Nominal line voltage
|
Un | 150 Vdc |
|
Max. DC operating voltage
|
Uc | 170 Vdc |
|
Max. frequency
|
f max. | > 10 MHz |
|
Insertion loss
|
< 1 dB |
|
|
Max. discharge current
max. withstand @ 8/20 µs by pole
|
Imax | 20 kA |
|
Nominal Discharge Current
C2 (1.2/50us / 8/20µs), 10 applications, X-X (Line/Line)
|
In | 5 kA |
|
Line inductance (± 10 %)
|
non |
|
|
Protection Level
C3 (10/1000μs), 300 applications@10 A, Y-Y (Line/Line)
|
Up | 220 V |
|
Impulse current
2 x 10/350µs Test - D1 Category
|
Iimp | 2.5 kA |
|
Max. Load current
|
IL | 300 mA |
|
Type of diagram
|
A |
|
|
Line resistance
|
< 4.7 Ohm |
|
Technology
|
GDT + R + Diode |
|
|
SPD configuration
|
4 pairs |
|
|
Connection to Network
|
By screw terminal: cross section 0.4-1.5mm² |
|
|
Format
|
Wall mounting box |
|
|
Mounting
|
Wall mounting by screws (not supplied) |
|
|
Housing material
|
Thermoplastic UL94 V-0 |
|
|
Operating temperature
|
Tu | -40/+85°C |
|
Protection rating
|
IP20 |
|
|
Failsafe mode
|
Short-circuit - transmision cut-off - fault mode 2 |
|
|
Spare module(s)
|
S480-T |
|
|
Remote signaling of disconnection
|
No |
|
|
Dimensions
|
See diagram |
|
|
Weight
|
0.138 kg |
|
Standards compliance
|
IEC 61643-21 / EN 61643-21 / UL497B |
|
|
Certification
|
UL listed |
|
|
Environmental standards
|
EU RoHS |
Datasheet