Contact : +33 1 41 23 50 23 (9:00 – 17:00 CEST)

Type 2 PV surge protector

DS50PV-600
Part Number 480401
DS50PV-600
  • Type 2 surge protector for PV
  • In : 20kA / Imax : 40kA
  • Pluggable
  • Remote signaling (option)
  • Certified UL1449 ed.5
  • Compliance EN 50539-11 / IEC 61643-31 / EN 61643-31

DS50PV are type 2 surge protectors are designed to protect against lightning surge voltages in photovoltaic power supply network. Based on the use of specific varistors, providing a protection in common mode or common and differential mode.

Select another reference:

SPD type
IEC

2

Nominal PV voltage
Uocstc

600 Vdc

Max. PV operating voltage
Ucpv

680 Vdc

Residual Current
Leakage current to Ground
Ipe

None

PV Permanent Operating current
Current consumption at Ucpv
Icpv

< 1 mA

Follow current
If

None

Nominal discharge current
15 x 8/20 µs impulses
In

20 kA

Max. discharge current
max. withstand @ 8/20 µs by pole
Imax

40 kA

Current withstand short circuit PV
Iscpv

1000 A

Protection mode(s)

Common mode

Protection level +/-
@ In (8/20µs)
Up

5.1 kV

Protection level +/PE (-/PE)
@ In (8/20µs)
Up

2.5 kV

Connection to Network

By screw terminals: 4-25mm² / by bus

Plugable

Yes

Mounting

Symmetrical rail 35 mm (EN 60715)

Housing material

Thermoplastic UL94 V-0

Operating temperature
Tu

-40/+85°C

Protection rating

IP20

Disconnection indicator

1 mechanical indicator by pole - Red/Green

Remote signaling of disconnection

Option DS50PVS-600 - output on changeover contact

Dimensions

See diagram

Weight

0.216 kg

Standards compliance

IEC 61643-31 / EN 61643-31 / EN 50539-11 / UL1449 ed.5

Certification

UL

Thermal disconnector

Internal