Contact : +33 1 41 23 50 23 (9:00 – 17:00 CEST)

Surge protector for LED lighting system Class 1

DSLP1-230L
Part Number 352913
DSLP1-230L
  • Type 2 (or 3) surge protectors for LED
  • Very compact (low profile)
  • DIN rail mounting
  • Screw terminal connection
  • Status indicator
  • Disconnection AC end of life
  • EN 61643-11, IEC 61643-11 compliance

DSLP range is an AC series surge protectors for DIN mountage create to protect LED systems. The surge protectors DSLP are verry compact to be integrated in the luminaires and are available in 2 connection modes (terminal screw or spring).

Select another reference:

SPD type
2 (or 3)
Isolation classe
I
Network
220-240 V Single-phase
AC system
TT-TN
Nominal line voltage
Un 230-277 Vac
Max. AC operating voltage
Uc 320 Vac
Max. load current
@25°C
IL 10 A
Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
UT 335 Vac withstand
Temporary Over Voltage (TOV) Characteristics - 120 mn
Without disconnection or with safety disconnection
UT 440 Vac disconnection
Temporary Over Voltage N/PE (TOV HT)
Without disconnection or with safety disconnection
UT 1200 V/300A/200 ms disconnection
Residual Current
Leakage current to Ground
Ipe None
Nominal discharge current
15 x 8/20 µs impulses
In 5 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 10 kA
Total Maximum discharge current
max. total withstand @ 8/20 µs
Imax Total 20 kA
Withstand on Combination waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
Uoc 10 kV / 5 kA
Withstand on overvoltages IEEE C62.41.1
10 kV / 10 kA
Protection mode(s)
Common/Differential mode
Protection level L/N
@ In (8/20µs)
Up L/N 1.5 kV
Protection level L/PE
@ In (8/20µs)
Up L/PE 1.5 kV
Admissible short-circuit current
Isccr 10 000 A
Technology
MOV+GDT
Connection to Network
Screw terminal 2.5 mm² max. Earthing conductor 2 mm² - length 60 cm
Mounting
Symmetrical rail 35 mm (EN 60715)
Housing material
Thermoplastic UL94 V-0
Operating temperature
Tu -40/+85°C
Protection rating
IP20
Failsafe mode
Disconnection from AC network
Disconnection indicator
LED green OFF and AC network cut-off
Voltage/operating indicator
Green Led ON
Dimensions
See diagram
Standards compliance
EN 61643-11 / IEC 61643-11
Certification
CB
Thermal disconnector
Internal
Installation ground fault breaker
Type 'S' or delayed