Coaxial surge protector for video transmission networks
Part Number: 632611
CNP06-B/MF
- Coaxial surge protector
- Multiples connectors
- Low insertion loss
- Easy installation
|
Network
|
coaxial DC-100 MHz |
|
|
Nominal line voltage
|
Un | 5 V |
|
Max. DC operating voltage
|
Uc | 10 Vdc |
|
Max. frequency
|
f max. | DC-100 MHz |
|
Insertion loss
|
≤ 0.5 dB |
|
|
Return loss
|
≥20 dB |
|
|
Impedance
|
50/75 ohms |
|
|
VSWR
|
< 1.3:1 |
|
|
Max. load current @25°C
|
IL | 0.5 A |
|
Operating current
Continious current at Uc
|
Ic | None |
|
Max. discharge current
max. withstand @ 8/20 µs by pole
|
Imax | 20 kA |
|
Nominal discharge current
C2 Category
|
In | 5 kA |
|
Protection mode(s)
|
Common mode |
|
|
Protection level
@ In (8/20 µs)
|
Up L/L | 20 V |
|
Protection level L/N
@ In (8/20µs)
|
Up L/N | 20 V |
|
Protection level L/PE
@ In (8/20µs)
|
Up L/PE | 20 V |
|
Impulse current
2 x 10/350µs Test - D1 Category
|
Iimp | 2.5 kA |
|
Max Power
|
4 W |
|
|
DC Pass
|
No |
|
Technology
|
GDT+TVS diode |
|
|
Connection to Network
|
Connector BNC Male/Female |
|
|
Format
|
Insulating box |
|
|
Mounting
|
On plate |
|
|
Housing material
|
Metal+plastic |
|
|
Operating temperature
|
Tu | -40/+85°C |
|
Protection rating
|
IP20 |
|
|
Outdoor application
|
No |
|
|
Failsafe mode
|
Short-circuit - transmision cut-off - fault mode 2 |
|
|
Disconnection indicator
|
Transmision interrupt |
|
|
Dimensions
|
See diagram |
|
Standards compliance
|
IEC 61643-21 / EN 61643-21 / UL497E |
Datasheet
UKCA