Contact : +33 1 41 23 50 23 (9:00 – 17:00 CEST)

D-sub dataline surge protector

DD9-6V
Part Number: 6148
DD9-6V
  • D-Sub surge protector
  • For RS422 communication lines
  • 9-pin connector
  • Fast and easy installation
  • Secondary protection

DD9ESD surge protector are designed to protect sensitive equipment linked to datalines equipped with D-sub connectors, as RS232, RS422 and RS485lines. They are equipped with D-sub connectors for fast and easy maintenance. In order to comply with the line configuration, all the wires are transmitted and protected.

Select another reference:

Network

RS422, RS423

Nominal line voltage
Un

5 Vdc

Max. DC operating voltage
Uc

6 Vdc

Max. frequency
f max.

> 10 MHz

Max. data rate

< 40 Mbps

Insertion loss

< 1 dB

Max. load current @25°C
IL

750 mA

Nominal Discharge Current
C2 (1.2/50us / 8/20µs), 10 applications, X-X (Line/Line)
In

400 A

Nominal Discharge Current, X-C (Line/Earth)
8/20µs Test x 10 - C2 Category
In L/PE

400 A

Line inductance (± 10 %)

non

Protection Level
C3 (10/1000μs), 300 applications@10 A, Y-Y (Line/Line)
Up

7.5 V

Line/Line Nominal discharge current
C2 Category
In L/L

400 A

Type of diagram

B

Line resistance

< 4.7 Ohm

Technology

SAD

SPD configuration

9 wires

Connection to Network

D-Sub 9 pts male/female Input/output

Format

In/out D-Sub connector unit

Mounting

On serial cable

Housing material

Thermoplastic UL94 V-0

Operating temperature
Tu

-40/+85°C

Protection rating

IP20

Failsafe mode

Short-circuit - transmision cut-off - fault mode 2

Disconnection indicator

Transmision interrupt

Spare module(s)

S480-24D3

Remote signaling of disconnection

No

Pinout

all wires transmitted and protected

Dimensions

See diagram

Weight

0.063 kg

Standards compliance

IEC 61643-21 / EN 61643-21 / UL497B

Certification

UL Listed

Environmental standards

EU RoHS