Type 2 (or 3) AC surge protector - one-phase

DS11-400
Part Number 341401
DS11-400
Availability:
€29.00 (excl. tax)

Available within 3 weeks

  • Type 2 (or 3) AC one-phase surge protector
  • In : 5 kA
  • Imax : 10 kA
  • Pluggable module by phase
  • Remote signaling option
  • EN 61643-11, IEC 61643-11, UL1449 ed.5 compliance

DS10 type2 AC surge protector are used mainly for primary protection of single and 3- phase networks at the main electrical panel. They provide common-mode or common and differential mode. This SPD is based on high energy varistor equipped with thermal disconnector and failure indicator, to comply with standards. The DS10 surge protectors are designed to be used in a multipolar configuration to protect single-phase, 3-phase or 3-phase+Neutral AC networks.They are sometimes associated with dedicated N/PE surge protector based on gas tube technology.

Select another reference:

SPD type
IEC 2 (or 3)
Network
230/400 V
Nominal line voltage
Un 400 Vac
Max. AC operating voltage
Uc 440 Vac
Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
UT 580 Vac withstand
Temporary Over Voltage (TOV) Characteristics - 120 mn
Without disconnection or with safety disconnection
UT 770 Vac disconnection
Residual Current
Leakage current to Ground
Ipe < 0.5 mA
Operating current
Continious current at Uc
Ic 0.5 mA
Follow current
If None
Nominal discharge current
15 x 8/20 µs impulses
In 5 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 10 kA
Total Maximum discharge current
max. total withstand @ 8/20 µs
Imax Total 10 kA
Withstand on Combination waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
Uoc 10 kV
Withstand on overvoltages IEEE C62.41.1
10 kV
Connection mode(s)
L/N or N/PE
Protection mode(s)
Common Mode or Differential Mode
Protection level
@ In (8/20µs)
Up 1.3 kV
Residual voltage at 5 kA
@ 5 kA (8/20µs)
Up-5kA 1.3 kV
Admissible short-circuit current
Isccr 25 000 A
Technology
MOV
SPD configuration
Single phase
Connection to Network
By screw terminals: 2.5-25mm² / by bus
Format
Plug-in modular box
Mounting
Symmetrical rail 35 mm (EN 60715)
Housing material
Thermoplastic UL94 V-0
Operating temperature
Tu -40/+85°C
Protection rating
IP20
Failsafe mode
Disconnection from AC network
Disconnection indicator
1 mechanical indicator
Spare module(s)
DSM10-400
Remote signaling of disconnection
option DS11S-400 : output on changeover contact
Dimensions
See diagram
Weight
0.153 kg
Standards compliance
IEC 61643-11 / EN 61643-11 / UL1449 ed.5
Certification
UL Recognized
Thermal disconnector
Internal
Installation ground fault breaker
Type 'S' or delayed
Back-up protection device
20 A min. - 125 A max. - Fuses type gG