Contact : +33 1 41 23 50 23 (9:00 – 17:00 CEST)

Type 2+3 AC surge protector - one-phase - pluggable with integrated fuse

DACF15-10-150
Part Number 821310111
DACF15-10-150
  • Type 2 (or 3) AC surge protector
  • Interne Disconnection device
  • Low caliber of the internal connector = systematic coordination with upstream circuit breaker
  • In : 5 kA
  • Imax : 15 kA
  • Pluggable module for each phase
  • Remote signaling option
  • EN 61643-11, IEC 61643-11, UL1449 ed.5 compliance

The special feature of this series is the integrated and monitored back-up fuse, which makes the use of an additional external back-up fuse unnecessary. Type 2 (or 3) DACF15 SPDs are used mainly for primary surge protection of single and 3-phase AC networks at the main switchboard. In addition to their thermal disconnector, the range is equipped with an internal fuse against short-circuit currents, which avoids the use of an external fuse or circuit-breaker as requested by standard. The operation of one of the both disconnectors will activate the indicator and the remote signalling (option). This compact solution simplifies the implementation and minimum space. The DACF15 surge protectors are designed to be used in a multipolar configuration to protect single-phase, 3-phase.

Select another reference:

SPD type
2 (or 3)
Max. AC operating voltage
Uc 150 Vac
Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
UT 180 Vac withstand
Temporary Over Voltage (TOV) Characteristics - 120 mn
Without disconnection or with safety disconnection
UT 230 Vac withstand
Residual Current
Leakage current to Ground
Ipe < 1 mA
Follow current
If None
Nominal discharge current
15 x 8/20 µs impulses
In 5 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 15 kA
Withstand on Combination waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
Uoc 10 kV
Protection level
@ In (8/20µs)
Up 0.6 kV
Admissible short-circuit current
Isccr 100 000 A
Technology
MOV
SPD configuration
Single phase
Connection to Network
By screw terminals: 2.5-25mm² (35mm² rigid)
Format
Plug-in modular box
Plugable
Yes
Mounting
Symmetrical rail 35 mm (EN 60715)
Housing material
Thermoplastic UL94 V-0
Operating temperature
Tu -40/+85°C
Protection rating
IP20
Failsafe mode
Disconnection from AC network
Disconnection indicator
1 mechanical indicator - Red/Green
Spare module(s)
MDACF15-150
Remote signaling of disconnection
option DACF15S-10-150 : output on changeover contact
Wiring for remote signaling
1.5 mm² max.
Dimensions
See diagram - 1TE (EN43880)
Weight
0.106 kg
Standards compliance
IEC 61643-11 / EN 61643-11
Thermal disconnector
Internal
Installation ground fault breaker
Type 'S' or delayed
Back-up protection device
internal (equivalent AC rating : 25 A, gG Type)
Integrated fuses
Yes