Contact : 01 41 23 50 35 (9h - 17h)
CITEL
Company History
Specialist in overvoltage protection
Locations
Test Facilities
citel and the environment
Service quality
Lightning Surges
Lightning and Transient overvoltages
The origin of overvoltages
Keraunic levels
Effects of lightning
Surge protectors
The "surge protection" solution
International Standards
Citel's VG Technology
SPD mandatory or not?
GDT overview
New range SPDs AC-DC
Products
AC Power
Photovoltaic
LED
Telecom
Dataline
Radiocommunication
GDT
Miscellaneous
Applications
Datacenter
E-Mobility
LED
Radiocommunication
Security Systems
Industrial Installation
Wind Turbine Installation
Domestic Photovoltaic
Industry Photovoltaic
Solar Farms
Energy storage sytems
Water Treatment
Services
Downloading
Webinars
partnership
News
Contact
Product ranges
AC Power
Photovoltaic
LED
Telecom
Dataline
Radiocommunication
Wind Turbine
GDT
Accessories
AC Power
Type 2 AC surge protector
DS73R-400
Type 2 AC surge protector - 3-phase
DS73R-400
Part Number:
491403
Re-inforced Type 2 AC Multipolar surge protector
In: 30 kA
Imax total: 210 kA
Pluggable module by phase
Remote signaling option
IEC 61643-11, EN 61643-11 compliance
UL1449 ed.5 approved
Datasheet
Installation Sheet
Tender specifications
Contact Us
DS70R type 2 AC surge protector are used mainly for primary protection of single and three-phase networks at the main electrical panel. They provide common-mode protection and are available in one-phase, single-phase, 3-phase and 3-phase+Neutral. This SPD is based on association of high energy varistors equipped with thermal disconnector and failure indicator, to comply with standards. The DS70R surge protectors are designed to be used in a multipolar configuration to protect single-phase, 3-phase or 3-phase+N AC networks. Each pole of the SPD is connected between Line(s) and PE and Neutral and PE.
Select another reference:
Electrical Properties
Mechanical Properties
Norms
Deconnector
Schemas
SPD type
2
Network
230/400 V 3-phase
AC system
IT
Nominal line voltage
Un
400 Vac
Max. AC operating voltage
Uc
440 Vac
Temporary Over Voltage (TOV) Charasteristics - 5 sec.
UT
580 Vac withstand
Temporary Over Voltage (TOV) Charasteristics - 120 mn
UT
770 Vac disconnection
Residual Current
Ipe
< 3 mA
Operating current
Ic
< 1 mA
Follow current
If
None
Nominal discharge current
In
30 kA
Max. discharge current
Imax
70 kA
Total Maximum discharge current
Imax Total
210 kA
Connection mode(s)
L/PE
Protection mode(s)
Common mode/Differential mode
Residuel voltage at 5 kA
Up-5kA
1.2 kV
Protection level L/PE
Up L/PE
1.8 kV
Residual voltage at 10 kA
Up-10kA
1.4 kV
Admissible short-circuit current
Isccr
25 000 A
Technology
MOV
SPD configuration
3-phase
Connection to Network
By screw terminals: 2.5-25mm² / by bus
Format
Plug-in modular box
Mounting
Symmetrical rail 35 mm (EN 60715)
Housing material
Thermoplastic UL94 V-0
Operating temperature
Tu
-40/+85°C
Protection rating
IP20
Failsafe mode
Disconnection from AC network
Disconnection indicator
2 mechanical indicators by pole
Spare module(s)
DSM70R-400
Remote signaling of disconnection
option DS73RS-400 : output on changeover contact
Dimensions
See diagram
Standards compliance
IEC 61643-11 / EN 61643-11 / UL1449 ed.5
Certification
CSA /EAC/UL
Thermal disconnector
Internal
Installation ground fault breaker
Type 'S' or delayed
Fuses
100 A min. - 125 A max. - Fuses type gG
×