Type 2+3 AC surge protector - single-phase

DS42VG-120/G
Part Number 461661
DS42VG-120/G
  • Type 2 + 3 AC Multipolar surge protector
  • In : 20 kA
  • Imax total: 100 kA
  • Pluggable module
  • Follow and operating current : none
  • No ageing
  • Optional remote signaling state
  • Optimized to TOV
  • EN 61643-11, IEC 61643-11, UL1449 ed.5 compliance

DS40VG Type 2 +3 AC surge protector, using CITEL's 'VG technology', to completely eliminate the leakAge and operation current while providing maximum discharge capacity and an optimized level of protection. The electric scheme includes a disconnector and its associated indicator .. The DS40VG surge protectors are designed to be used in a multipolar configuration to protect single-phase, 3-phase or 3-phase+N AC networks.

Select another reference:

SPD type
2+3
Network
120 V single-phase
AC system
TT-TN
Nominal line voltage
Un 120 Vac
Max. AC operating voltage
Uc 150 Vac
Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
UT 180 Vac withstand
Temporary Over Voltage (TOV) Characteristics - 120 mn
Without disconnection or with safety disconnection
UT 230 Vac withstand
Temporary Over Voltage N/PE (TOV HT)
Without disconnection or with safety disconnection
UT 1200 V/300A/200 ms withstand
Residual Current
Leakage current to Ground
Ipe None
Follow current
If None
Nominal discharge current
15 x 8/20 µs impulses
In 20 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 40 kA
Total Maximum discharge current
max. total withstand @ 8/20 µs
Imax Total 80 kA
Withstand on Combination waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
Uoc 6 kV
Withstand on overvoltages IEEE C62.41.1
20 kV
Connection mode(s)
L/N and N/PE
Protection mode(s)
Common/Differential mode
Residual voltage
@ In (8/20 µs)
Up-in 0.6 kV
Protection level L/N
@ In (8/20µs)
Up L/N 1.25 kV
Protection level N/PE
@ In (8/20µs)
Up N/PE 1.5 kV
Admissible short-circuit current
Isccr 25 000 A
Technology
VG Technology (MOV+GSG)
SPD configuration
Single phase
Connection to Network
By screw terminals: 2.5-25mm² / by bus
Format
Plug-in modular box
Mounting
Symmetrical rail 35 mm (EN 60715)
Housing material
Thermoplastic UL94 V-0
Operating temperature
Tu -40/+85°C
Protection rating
IP20
Failsafe mode
Disconnection from AC network
Disconnection indicator
1 mechanical indicator by pole
Spare module(s)
DSM40VG-120+DSM80G-600
Remote signaling of disconnection
option DS42VGS-120/G : output on changeover contact
Dimensions
See diagram
Standards compliance
IEC 61643-11 / EN 61643-11 / UL1449 ed.5
Certification
UL Recognized
Thermal disconnector
Internal
Installation ground fault breaker
Type 'S' or delayed
Back-up protection device
Fuses type gG - 50 A