Type 2 AC surge protector - 1-pole - pluggable
DS41-600
DS41-600
Part Number: 331501
  • Type 2 AC surge protector
  • In : 20 kA
  • Imax : 40 kA
  • Pluggable module for each phase
  • Remote signaling option
  • NF EN 61643-11, CEI 61643-11 compliance
  • UL1449 ed.4
Installation Sheet

used mainly for primary protection of single and 4- phase networks at the main electrical panel. They provide common-mode or common and differential mode. This SPD is based on high energy varistor equipped with thermal disconnector and failure indicator, to comply with standards. The DS40 surge protectors are designed to be used in a multipolar configuration to protect single-phase, 3-phase or 3-phase+Neutral AC networks.They are sometimes associated with dedicated N/PE surge protector based on gas tube technology.

Select another reference:

SPD type 2
Network 347/600 V
Nominal line voltage Un 377 Vac
Max. AC operating voltage L-N Uc 660 Vac
Temporary Over Voltage (TOV) Charasteristics - 5 sec. UT 870 Vac withstand
Temporary Over Voltage (TOV) Charasteristics - 120 mn UT 1150 Vac disconnection
Residual Current Ipe < 0.5 mA
Operating current Ic 0.5 mA
Follow current If None
Nominal discharge current In 20 kA
Max. discharge current Imax 40 kA
Connection mode(s) L/PE and N/PE
Protection mode(s) Common Mode or Differential Mode
Protection level Up 3.2 kV
Admissible short-circuit current Isccr 25000 A
Technology MOV
SPD configuration 1-pole
Connection to Network By screw terminals: 2.5-25 mm² / by bus
Format Plug-in modular box
Mounting Symmetrical rail 35 mm (EN60715)
Housing material Thermoplastic UL94-V0
Operating temperature -40/+85°C
Protection rating IP20
Failsafe mode Disconnection
Disconnection indicator 1 mechanical indicator
Spare module(s) DSM40-600
Remote signaling of disconnection option DS41S-600 : output on changeover contact
Dimensions See diagram
Standards compliance IEC 61643-11 / EN 61643-11 / UL1449 4ed.
Certification UL / CSA /EAC