Type 2 AC surge protector - 3-phase+N
DACF25-40-275
Part Number: 821410214
- Type 2 AC Multipolar surge protector
- In : 15 kA
- Imax total : 100 kA
- Internal Fuse
- Pluggable module for each phase
- Remote signaling option
- EN 61643-11, IEC 61643-11 certified
- UL1449 ed.4 compliance
Type 2 DACF25 SPDs are used mainly for primary surge protection of single and 3-phase AC networks at the main switchboard.
In addition to their thermal disconnector, the range is equipped with a internal fuse against short-circuit currents, which avoidsthe use of a external fuse or circuit-breaker as requested by standard.
The operation of one of the both disconnectors will activate the indicator and the remote signalling (option).
This compact solution simplifies the implementation and minimum space.
The DACF25 surge protectors are designed to be used in a multipolar configuration to protect single-phase, 3-phase.
Select another reference:
- DACF25-10-150
- DACF25-10-275
- DACF25-10-320
- DACF25-10-440
- DACF25-11-150
- DACF25-11-275
- DACF25-11-320
- DACF25-20-150
- DACF25-20-275
- DACF25-20-320
- DACF25-20-440
- DACF25-30-150
- DACF25-30-275
- DACF25-30-320
- DACF25-30-440
- DACF25-31-150
- DACF25-31-275
- DACF25-31-320
- DACF25-40-150
- DACF25-40-275
- DACF25-40-320
- DACF25-40-440
SPD type | 2 | |
Network | 230/400 V 3-phase+N | |
AC system | TNS | |
Max. AC operating voltage | Uc | 275 Vac |
Temporary Over Voltage (TOV) Charasteristics - 5 sec. | UT | 335 Vac withstand |
Temporary Over Voltage (TOV) Charasteristics - 120 mn | UT | 440 Vac disconnection |
Residual Current | Ipe | < 1 mA |
Follow current | If | None |
Nominal discharge current | In | 15 kA |
Max. discharge current | Imax | 25 kA |
Total Maximum discharge current | Imax Total | 100 kA |
Connection mode(s) | L/PE and N/PE | |
Protection level L/PE | Up L/PE | 1.25 kV |
Protection level N/PE at 5 kA | Up-5kA | 1 kV |
Residual voltage L/PE at 5 kA | Up-5kA | 1 kV |
Admissible short-circuit current | Isccr | 100 000 A |
Technology | MOV | |
SPD configuration | 3-phase+Neutral | |
Connection to Network | By screw terminals: 2.5-25 mm² (35 mm² rigid) | |
Format | Plug-in modular box | |
Mounting | Symmetrical rail 35 mm (DIN 60715) | |
Housing material | Thermoplastic UL94 V-0 | |
Operating temperature | Tu | -40/+85°C |
Protection rating | IP20 | |
Failsafe mode | Disconnection from AC network | |
Disconnection indicator | 1 mechanical indicator by pole - Red/Green | |
Spare module(s) | MDACF25-275 | |
Remote signaling of disconnection | option DACF25S-40-275 : output on changeover contact | |
Wiring for remote signaling | 1.5 mm² max. | |
Max. Voltage/Current for remote signaling | 250 V / 0.5 A (AC) / 30 V / 3 A (DC) | |
Dimensions | See diagram - 4TE (EN43880) | |
Weight | 0.383 kg |
Standards compliance | IEC 61643-11 / EN 61643-11 / UL1449 4ed. | |
Certification | KEMA / EAC |
Thermal disconnector | Internal | |
Installation ground fault breaker | Type 'S' or delayed | |
Fuses | internal (equivalent AC rating : 40 A, gG Type) |