Type 2 AC surge protector - 3-phase
DAC50-30-320
DAC50-30-320
Part Number: 821110313
  • Type 2 AC surge protector
  • In : 20 kA
  • Imax : 50 kA
  • Pluggable module for each phase
  • Remote signaling option
  • NF EN 61643-11, IEC 61643-11 compliance
Installation Sheet

The pluggable surge protectors Type 2 DAC50, are designed to protect AC powerline at the main switchboard of the installation.

These SPDs are based on high energy varistor equipped with thermal disconnector and failure indicator, to comply with standards and to provide a maximum protection efficiency, an high impulse current capability and a improved reliability.

The surge protectors DAC50 are available in multipolar version and in several voltages to protect single or 3-phase networks.



SPD type
following IEC test
2
Network
230/400 V 3-phase
AC system
TNC
Max. AC operating voltage L-N
320 Vac
Temporary Over Voltage (TOV) Charasteristics - 5 sec.
without disconnection
335 Vac withstand
Temporary Over Voltage (TOV) Charasteristics - 120 mn
without disconnection or with safety disconnection
440 Vac disconnection
Residual Current
Leakage current to Ground
< 1 mA
Follow current
None
Nominal discharge current
15 x 8/20 µs impulses
20 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
50 kA
Total Maximal discharge current
max. total withstand @ 8/20 µs
150 kA
Admissible short-circuit current
50000 A
Protection level L/PE
@ In (8/20µs)
1.5 kV
Technology MOV
SPD configuration 3-phase
Connection to Network By screw terminals: 2.5-25 mm² / by bus
Format
Plug-in modular box
Mounting
Symmetrical rail 35 mm (EN60715)
Housing material Thermoplastic UL94-V0
Operating temperature -40/+85°C
Protection rating IP20
Failsafe behavior Disconnection
Disconnection indicator 1 mechanical indicator by pole
Spare module(s)
MDAC50-320
Remote signaling of disconnection
option DAC50S-30-320 : output on changeover contact
Dimensions
See diagram
Certification
OVE
Standards compliance
IEC 61643-11 / EN 61643-11 / UL1449 4ed.
Installation ground fault breaker Type 'S' or delayed
Thermal disconnector Internal
Fuses
Fuses Type gG - 125 A