Type 1+2+3 AC surge protector - Single phase
Part Number: 571572
DS132VGS-230/G
- Discover our latest innovation : the DAC1-13VGS-11-275
- Type 1 + 2 + 3 AC surge protector
- In : 20 kA
- Iimp total : 25 kA on 10/350µs impulse
- Pluggable module
- Optimized to TOV
- Remote signaling
- EN 61643-11, IEC 61643-11 and UL 1449 ed.4 compliance
The DS130VG is an extreme duty Type 1+2+3 AC surge protector device designed to protect at the entrance of the electrical installation.
This SPD is particularly useful in a high lightning density area where the risk of heavy surge current or even direct strike is high (eg: buildings equipped with lightning rods).
The DS130VG is one-pole SPD and can be used in common mode or common and differential mode.
DS130VG AC surge protectors are designed to be connected in multi-pole configuration to protect single-phase, 3-phase and 3-phase+Neutral AC networks, sometimes associated with a dedicated N/PE SPD.
Certificates
|
SPD type
|
IEC | 1+2+3 |
|
Network
|
230 V single-phase |
|
|
AC system
|
TT-TN |
|
|
Nominal line voltage
|
Un | 230 Vac |
|
Max. AC operating voltage
|
Uc | 255 Vac |
|
Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
|
UT | 335 Vac withstand |
|
Temporary Over Voltage (TOV) Characteristics - 120 mn
Without disconnection or with safety disconnection
|
UT | 440 Vac withstand |
|
Temporary Over Voltage N/PE (TOV HT)
Without disconnection or with safety disconnection
|
UT | 1200 V/300A/200 ms withstand |
|
Residual Current
Leakage current to Ground
|
Ipe | None |
|
Follow current
|
If | None |
|
Nominal discharge current
15 x 8/20 µs impulses
|
In | 20 kA |
|
Max. discharge current
max. withstand @ 8/20 µs by pole
|
Imax | 50 kA |
|
Impulse current by pole
max. withstand 10/350µs by pole
|
Iimp | 12.5 kA |
|
Total lightning current
max. total withstand @ 10/350µs
|
Itotal | 25 kA |
|
Withstand on Combination waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
|
Uoc | 20 kV |
|
Withstand on overvoltages IEEE C62.41.1
|
20 kV |
|
|
Specific energy by pole
max. withstand 10/350 µs
|
W/R | 40 kJ/ohm |
|
Connection mode(s)
|
L/N and N/PE |
|
|
Protection mode(s)
|
Common/Differential mode |
|
|
Residual voltage
@ In (8/20 µs)
|
Up-in | 0.6 kV |
|
Protection level L/N
@ In (8/20µs)
|
Up L/N | 1.25 kV |
|
Protection level N/PE
@ In (8/20µs)
|
Up N/PE | 1.5 kV |
|
Admissible short-circuit current
|
Isccr | 25 000 A |
|
Technology
|
VG Technology (MOV+GSG) |
|
|
SPD configuration
|
Single phase |
|
|
Connection to Network
|
By screw terminals: 2.5-25mm² / by bus |
|
|
Format
|
Plug-in modular box |
|
|
Mounting
|
Symmetrical rail 35 mm (EN 60715) |
|
|
Housing material
|
Thermoplastic UL94 V-0 |
|
|
Operating temperature
|
Tu | -40/+85°C |
|
Protection rating
|
IP20 |
|
|
Failsafe mode
|
Disconnection from AC network |
|
|
Disconnection indicator
|
1 mechanical indicator by pole |
|
|
Spare module(s)
|
DSM130VG-230 + DSM130VG-230/G |
|
|
Remote signaling of disconnection
|
Output on changeover contact |
|
|
Dimensions
|
See diagram |
|
|
Weight
|
0.246 kg |
|
Standards compliance
|
IEC 61643-11 / EN 61643-11 / UL1449 ed.5 |
|
Thermal disconnector
|
Internal |
|
|
Installation ground fault breaker
|
Type 'S' or delayed |
|
|
Back-up protection device
|
Fuses Type gG - 125 A |