Contact : +33 1 41 23 50 23 (9:00 – 17:00 CEST)

Type 1 and Type 2 DC surge protector

DS252E-420DC
Part Number: 64005
DS252E-420DC
  • Type 1 + 2 DC 400 V surge protector
  • Iimp: 25 kA
  • Internal disconnection with indicator
  • Remote signaling
  • EN 61643-11, IEC 61643-11 compliance

DS25xE-420DC surge protectors are designed to protect equipment connected to DC power supplies from lightning surges.

Select another reference:

Network

400 Vdc

Max. DC operating voltage
Uc

420 Vdc

Residual Current
Leakage current to Ground
Ipe

< 3 mA

Follow current
If

None

Nominal discharge current
15 x 8/20 µs impulses
In

25 kA

Max. discharge current
max. withstand @ 8/20 µs by pole
Imax

140 kA

Impulse current by pole
max. withstand 10/350µs by pole
Iimp

25 kA

Total lightning current
max. total withstand @ 10/350µs
Itotal

50 kA

Specific energy by pole
max. withstand 10/350 µs
W/R

156 kJ/ohm

Protection level +/PE (-/PE)
@ In (8/20µs)
Up

1.5 kV

Admissible short-circuit current
Isccr

50 000 A

Connection to Network

By screw terminals: 6-35mm² / by bus

Mounting

Symmetrical rail 35 mm (EN 60715)

Housing material

Thermoplastic UL94 V-0

Operating temperature
Tu

-40/+85°C

Protection rating

IP20

Disconnection indicator

1 mechanical indicator by pole

Remote signaling of disconnection

Output on changeover contact

Dimensions

See diagram

Weight

0.55 kg

Standards compliance

IEC 61643-11 / EN 61643-11

Certification
Thermal disconnector

Internal

Back-up protection device

Fuses type gG - 315 A