1-pole Type 1 and Type 2 SPD for 48 Vdc
DS250E-48DC
DS250E-48DC
Part Number: 63909
  • 1-pole surge protector 48 Vdc
  • Type 1 and Type 2 application
  • In 25 kA / Imax 70 kA
  • Remote signaling
  • Iimp 25 kA
  • IEC 61643-11 and EN61643-11 compliance
Installation Sheet

DS250E-48DC surge protectors are designed to protect equipment connected to DC power supplies from lightning surges

Select another reference:

SPD type 1+2
Network 48 Vdc
Nominal line voltage Un 48 Vdc
Nominal DC voltage Un-dc 48 Vdc
Max. DC operating voltage Uc 75 Vdc
Operating current Ic < 0.1 mA
Follow current If None
Nominal discharge current In 25 kA
Max. discharge current Imax 70 kA
Total Maximal discharge current Imax Total 140 kA
Impulse current by pole Iimp 25 kA
Specific energy by pole W/R 156 kJ/ohm
Connection mode(s) +/PE or -/PE
Protection mode(s) Common mode
Protection level Up 0.5 kV
Technology MOV
SPD configuration 1-pole
Connection to Network By screw terminals : 6-35 mm² / by bus
Format 1-pole modular box
Mounting Symmetrical rail 35 mm (EN60715)
Housing material Thermoplastic UL94-V0
Operating temperature -40/+85°C
Protection rating IP20
Failsafe mode Disconnection
Disconnection indicator 1 mechanical indicator
Remote signaling of disconnection Output on changeover contact
Dimensions See diagram
Standards compliance IEC 61643-11 / EN 61643-11 / UL1449 4ed.
Certification UL / EAC / TUV