Type 2 AC surge protector - 3-phase

DU33S-1000/WD
Part Number 302113
DU33S-1000/WD
  • Type 2 AC Multipolar surge protector
  • In : 15 kA
  • Imax total : 120 kA
  • Remote signaling for each pole
  • NF EN 61643-11, IEC 61643-11 compliance

Used mainly for wind turbines 3- phase networks at the generator and convertor. This type composed of 3-pole DU30S-1000/WD associated with dedicated surge protector DU100G-3500/WD, this module based on gas tube technology to realize protcetion for harmonic interference which mainly appeared in wind turbines. This surge protectors are designed to be used in a multipolar configuration to protect 3-phase AC networks.

Select another reference:

SPD type
IEC

2

Network

400/690 Vac 3-phase

AC system

TNC-IT

Nominal line voltage
Un

690 Vac

Max. AC operating voltage
Uc

1000 Vac

Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
UT

1200 Vac withstand

Residual Current
Leakage current to Ground
Ipe

None

Operating current
Continious current at Uc
Ic

0.5 mA

Follow current
If

None

Nominal discharge current
15 x 8/20 µs impulses
In

15 kA

Max. discharge current
max. withstand @ 8/20 µs by pole
Imax

30 kA

Total Maximum discharge current
max. total withstand @ 8/20 µs
Imax Total

120 kA

Connection mode(s)

L/PE

Protection mode(s)

Common mode

Protection level L/PE
@ In (8/20µs)
Up L/PE

4.2 kV

Admissible short-circuit current
Isccr

25 000 A

Technology

MOV

SPD configuration

3-phase

Connection to Network

By screw terminals: 2.5-25mm² / by bus

Format

Plug-in modular box

Mounting

Symmetrical rail 35 mm (EN 60715)

Housing material

Thermoplastic UL94 V-0

Operating temperature
Tu

-40/+85°C

Protection rating

IP20

Failsafe mode

Disconnection from AC network

Disconnection indicator

3 mechanical indicators

Remote signaling of disconnection

output on changeover contact

Wiring for remote signaling

1.5 mm² max.

Max. Voltage/Current for remote signaling

250 V / 0.5 A (AC) / 30 V / 3 A (DC)

Dimensions

See diagram

Standards compliance

EN 61643-11 / IEC 61643-11

Certification
Thermal disconnector

Internal

Installation ground fault breaker

Type 'S' or delayed

Back-up protection device

Fuses type gG - 100A