Type 2 AC surge protector - 3-phase
Part Number: 821115544
DAC50S-31-760-2600DC
- Type 2 AC surge protector
- In : 20 kA
- Imax : 50 kA
- Pluggable module for each phase
- Remote signaling
- EN 61643-11, IEC 61643-11 compliance
The pluggable surge protectors Type 2 DAC50, are designed to protect AC powerline at the main switchboard of the installation.
These SPDs are based on high energy varistor equipped with thermal disconnector and failure indicator, to comply with standards and to provide a maximum protection efficiency, a high impulse current capability and an improved reliability.
The surge protectors DAC50 are available in multipolar version and in several voltages to protect single or 3-phase networks.
Select another reference:
DAC50S-31-760-2600DC
Certificates
|
SPD type
|
IEC | 2 |
|
Network
|
400/690 Vac 3-phase |
|
|
AC system
|
TNC-IT |
|
|
Max. AC operating voltage
|
Uc | 800 Vac |
|
Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
|
UT | 2200 Vac withstand |
|
Residual Current
Leakage current to Ground
|
Ipe | None |
|
Follow current
|
If | None |
|
Nominal discharge current
15 x 8/20 µs impulses
|
In | 20 kA |
|
Max. discharge current
max. withstand @ 8/20 µs by pole
|
Imax | 50 kA |
|
Total Maximum discharge current
max. total withstand @ 8/20 µs
|
Imax Total | 50 kA |
|
Protection mode(s)
|
L/PE |
|
|
Protection level
@ In (8/20µs)
|
Up | ≤ 4 kV |
|
Admissible short-circuit current
|
Isccr | 50 000 A |
|
Network type
|
DC |
|
|
Technology
|
MOV+GDT |
|
|
SPD configuration
|
3+1-Y diagram |
|
|
Connection to Network
|
By screw terminals: 2.5-25mm² |
|
|
Format
|
Plug-in modular box |
|
|
Plugable
|
Yes |
|
|
Mounting
|
Symmetrical rail 35 mm (EN 60715) |
|
|
Housing material
|
Thermoplastic UL94 V-0 |
|
|
Operating temperature
|
Tu | -40/+85°C |
|
Protection rating
|
IP20 |
|
|
Failsafe mode
|
Disconnection from AC network |
|
|
Disconnection indicator
|
1 mechanical indicator by pole - Red/Green |
|
|
Spare module(s)
|
MDAC50-320+MDAC50G-320 |
|
|
Remote signaling of disconnection
|
output on changeover contact |
|
|
Wiring for remote signaling
|
1.5 mm² max. |
|
|
Max. Voltage/Current for remote signaling
|
250 V / 0.5 A (AC) / 30 V / 3 A (DC) |
|
|
Dimensions
|
See diagram - 4TE (EN43880) |
|
|
Weight
|
0.443 kg |
|
Standards compliance
|
IEC 61643-11 / EN 61643-11 / UL1449 ed.5 |
|
Thermal disconnector
|
Internal |
|
|
Installation ground fault breaker
|
Type 'S' or delayed |
|
|
Back-up protection device
|
50 A min. - 125 A max. - Fuses Type gG |
Datasheet