Contact : +33 1 41 23 50 30 (9:00 – 17:00 CEST)

RJ11 surge protector for 1 telephone line

MJ6-1T-UL
Part Number 560422
MJ6-1T-UL
  • Telecom line surge protector
  • PSTN, ADSL2, VDSL
  • 1-pair + Shielded
  • Instantaneous installation
  • RJ11 connector
  • UL497A

The MJ6-1T/D surge protector is designed to protect sensitive telecom terminals against lightning surges. They are equipped with standard telecom connection allowing easy and intantaneous maintenance. Compatible with RJ11 connector it protects one PSTN or ADSL2 line Wall mounting

Select another reference:

Network
Telephone Line, ADSL2, VDSL2, 1 pair
Nominal line voltage
Un 150 Vdc
Max. AC operating voltage
Uc 150 Vac
Max. DC operating voltage
Uc 170 Vdc
Max. frequency
f max. > 10 MHz
Max. data rate
30 Mbps
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 20 kA
Line inductance
No
Protection level
@ In (8/20µs)
Up 220 V
Protection level
Following the test category C3 (IEC61643-21) - Line/Line
Up 220 V
Protection level
Following the test category C3 (IEC61643-21) - Line/PE
Up 20 V
Protection level L/N
@ In (8/20µs)
Up L/N 220 V
Protection level L/PE
@ In (8/20µs)
Up L/PE 220 V
Line/Line Nominal discharge current
C2 Category
In L/L 2500 A
Nominal Discharge Current, X-C (Line/Earth)
8/20µs Test x 10 - C2 Category
In L/PE 2500 A
Line resistance
< 4.7 Ohm
Network type
Data Communication
Technology
GDT+Clamping diode
SPD configuration
1-pair+shielded
Connection to Network
RJ11 connector female input/output
Format
RJ11 Connector
Mounting
Mounting flange,Screw lug
Housing material
Aluminium
Operating temperature
Tu -40/+85°C
Protection rating
IP20
Outdoor application
No
Failsafe mode
Short-circuit
Disconnection indicator
Transmission interrupt
Spare module(s)
DLAM-170
Remote signaling of disconnection
No
Pinout
1-pair (3-4)
Dimensions
See diagram
Standards compliance
IEC 61643-21 / EN 61643-21 / UL497A