Contact : +33 1 41 23 50 23 (9:00 – 17:00 CEST)

1-pair Data surge protector

MDL-28-R
Part Number: 831611
MDL-28-R
  • Data line protection
  • High energy protection in common-mode
  • Low clamping level in differential mode
  • Galvanic isolation to earth connection
  • Indoor applications, IP20 (NEMA 2)
  • Plastic enclosure, UL94-V0
  • Certified acc. to IEC/EN 61643-21
  • Location and test categories: C2, C3

MDL compact surge protective devices (SPDs) are designed to protect the DALI control-lines of lighting systems, typically used in tunnel applications, from the effects of lightning and transient over voltages. These SPDs are installed on mounting plates, typically within the luminaires itself or in the lighting cabinets. MDL SPDs protect 1-pair (2-wire) lines and feature a compact non-pluggable (monobloc) enclosure based on Citels' well-known MLPC series shape. The hybrid protection circuit combining a gas discharge tube and clamping diodes offers a full-mode protection across the data-lines by additionally providing specific protection for the signalling ground wire (where needed).

Select another reference:

Network

Digital communication (2-Wire)

Protection modes (network)

CM / DM

Lightning Protection Zones (LPZ)

1 - 3

Nominal line voltage
Un

24 Vdc

Max. DC operating voltage
Uc

28 Vdc

Cut-off frequency
-3dB, 100 ohm system
f max.

> 30 MHz

Cut-off frequency
-1dB, 100 ohm system
f max.

> 10 MHz

Max. load current @25°C
IL

500 mA

Signal rise/fall times, to BS EN IEC 62386-101:2022
tʳⁱˢᵉ, tᶠᵃˡˡ

3 µs

Nominal discharge current
C2 (1.2/50us / 8/20µs), 10 applications X-C (Line/Earth)
In

4 kV / 2 kA

Nominal discharge current
CWG (1.2/50us / 8/20us) with 42 ohms, X-X (Line-Line), to IEC 61000-4-5 (unshielded asymmetric)
In

800 V / 20 A

Max. discharge current
C2 (1.2/50µs / 8/20µs), 10 applications, X-C (Line-Earth)

20 kV / 10kA

Protection Level
C3 (10/1000μs), 300 applications@10 A, Y-Y (Line/Line)
Up

< 40 V

Protection Level
C2 (1.2/50µs / 8/20µs), 10 applications, Y-C (Line-Earth)
Up

< 1000 V

Protection Level
CWG (1.2/50µs / 8/20µs) with 42 ohms, Y-Y (Line-Line), to IEC 61000-4-5 (unshielded asymmetric)
Up

< 48 V

Line resistance (± 10%)

< 0.2 ohms

Capacitance
@1MHz X-C (Line/Earth)
C

< 10 pF

Capacitance
@1MHz X-X (Line-Line)
C

< 30 pF

Technology

GDT+TVS diode

SPD configuration

Data-pair, plus PE

Connection to Network

2 spring terminals opposite side in/out - wire 1.5mm² max.

Format

Plastic Enclosure with connectors input/output

Mounting

On plate

Housing material

Thermoplastic UL94 V-0

Operating and storage temperature

-40/+85°C

Ingress Protection rating

IP20 (NEMA 2)

Failsafe mode

Transmission cut-off - Fault mode 2 (short-circuit)

Dimensions

See diagram

Weight

0.035 kg / 0.09 lbs

Standards compliance

IEC 61643-21 / EN 61643-21/ IEC 61000-4-5 / IEC 62386-101

Certification

KEMA