Type 1+2 PV surge protector - 1000 Vdc
DS50PV-1500/12KT1
Part Number: 482523
- Type 1+2 surge protector for Photovoltaic
- Impulse currents Iimp/Itotal : 6.25/12.5 kA (10/350µs)
- Common/Differential mode protection
- Remote signaling (option)
- EN 50539-11 / IEC 61643-31 compliance
Select another reference:
SPD type | 1+2 | |
Network | PV network 1250 Vdc | |
Nominal PV voltage | Uocstc | 1250 Vdc |
Max. PV operating voltage | Ucpv | 1500 Vdc |
Residual Current | Ipe | < 0.3 mA |
PV Permanent Operating current | Icpv | < 0.1 mA |
Follow current | If | None |
Nominal discharge current | In | 15 kA |
Max. discharge current | Imax | 40 kA |
Total Maximum discharge current | Imax Total | 60 kA |
Impulse current by pole | Iimp | 6.25 kA |
Total lightning current | Itotal | 12.5 kA |
Current withstand short circuit PV | Iscpv | 15000 A |
Connection mode(s) | +/-/PE | |
Protection mode(s) | Common/Differential mode | |
Protection level +/- | Up | 5.3 kV |
Protection level +/PE (-/PE) | Up | 5.3 kV |
Technology | MOV | |
Connection to Network | Screw terminals: 2.5-25mm² | |
Format | Plug-in modular box | |
Mounting | Symmetrical rail 35 mm (DIN 60715) | |
Housing material | Thermoplastic UL94 V-0 | |
Operating temperature | Tu | -40/+85°C |
Protection rating | IP20 | |
Disconnection indicator | 1 mechanical indicator by pole | |
Spare module(s) | DSM50PV-1500/12KT1 | |
Remote signaling of disconnection | Option DS50PVS-1500/12KT1 - output on changeover contact | |
Dimensions | See diagram |
Standards compliance | IEC 61643-31 / EN 61643-31 / EN 50539-11 | |
Certification | EAC / TUV |
Thermal disconnector | Internal | |
Fuses | Without |