Contact : +33 1 41 23 50 23 (9:00 – 17:00 CEST)

SPD for LED lighting system Class 2 - Mechanical status indicator

DLPM2-230L
Part Number 355933
DLPM2-230L
Availability:
€25.00 (excl. tax)

Available within 3 weeks

  • Type 2 (or 3) surge protectors for LED
  • For single-phase or biphase network
  • Very compact (low profile)
  • DIN rail mounting
  • Screw terminal connection
  • Mechanical status indicator
  • Disconnection AC end of life
  • EN 61643-11 compliance

The DLPM range is a series of DIN-mount AC surge protector designed to be installed inside the cutouts: his compact size and lower height make it compatible with the DIN rail mounting of its enclosures. This range has a mechanical disconnect indicator.


SPD type
IEC 2 (or 3)
Isolation classe
II
Network
220-240 V Single-phase
AC system
TT-TN
Max. AC operating voltage
Uc 320 Vac
Max. load current
@25°C
IL 10 A
Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
UT 335 Vac withstand
Temporary Over Voltage (TOV) Characteristics - 120 mn
Without disconnection or with safety disconnection
UT 440 Vac disconnection
Nominal discharge current
15 x 8/20 µs impulses
In 5 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 10 kA
Withstand on Combination waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
Uoc 10 kV
Connection mode(s)
L/N
Protection mode(s)
Differential Mode
Protection level L/N
@ In (8/20µs)
Up L/N 1.5 kV
Admissible short-circuit current
Isccr 10 000 A
Technology
MOV
Mounting
Symmetrical rail 35 mm (EN 60715)
Housing material
Thermoplastic UL94 V-0
Operating temperature
Tu -40/+85°C
Protection rating
IP20
Failsafe mode
Disconnection and AC line cut-off
Disconnection indicator
LED green OFF and AC network cut-off
Voltage/operating indicator
Green Led ON
Remote signaling of disconnection
No
Dimensions
See diagram
Weight
0.063 kg
Standards compliance
EN 61643-11 / IEC 61643-11
Thermal disconnector
Internal
Installation ground fault breaker
Type 'S' or delayed