Compact single-phase type 2 (or 3) surge protector - 230 V - Monobloc
DS98-230/G
DS98-230/G
Part Number: 350923
  • Cost effective single-phase surge protector
  • Type 2 (or 3) monobloc
  • In : 5 kA
  • Imax : 10 kA
  • Common/Differential mode
  • End of life controlled : disconnection and indication
  • Remote signaling (option)
  • EN 61643-11, CEI 61643-11, UL1449 ed.4 compliance
Installation Sheet

DS98L AC surge protector is used for the 'secondary' protection of the single-phase networks against the surge voltages creating by lightning. DS98 is equipped with in-line safety disconnectin and double output connection. The disconnection will be indicate by the turn on of the red led in the front. Very compact, the DS98L surge protector must be installed close by the equipment to protect, downstream a 'primary' surge protector. DS98L provides both a common and differential mode protection.


Select another reference:

SPD type
following IEC test
2 (ou 3)
Network
230 V single-phase
AC system
TT-TN
Nominal line voltage
230 Vac
Max. AC operating voltage L-N 275 Vac
Max. load current
16 A
Temporary Over Voltage (TOV) Charasteristics - 5 sec.
without disconnection
335 Vac withstand
Temporary Over Voltage (TOV) Charasteristics - 120 mn
without disconnection or with safety disconnection
440 Vac disconnection
Temporary Over Voltage N/PE (TOV HT)
without disconnection or with safety disconnection
1200 V/300A/200 ms withstand
Residual Current
Leakage current to Ground
None
Follow current
None
Nominal discharge current
15 x 8/20 µs impulses
5 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
10 kA
Withstand on Combinaison waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
10 kV
Withstand on overvoltages IEEE C62.41.1 10 kV
Admissible short-circuit current 10000 A
Protection mode(s)
Common/Differential mode
Protection level CM/DM
@ In (8/20µs)
1.5 kV / 1.5 kV
 
SPD configuration Single phase
Connection to Network by screw terminals : 2.5 mm² max.
Format Plug-in modular box
Mounting Symmetrical rail 35 mm (EN60715)
Housing material Thermoplastic UL94-V0
Operating temperature -40/+85°C
Protection rating IP20
Outdoor application
False
Failsafe behavior Disconnection SPD
Disconnection indicator Red light on
Remote signaling of disconnection option DS98S-230/G
Dimensions
See diagram
Standards compliance IEC 61643-11 / EN 61643-11 / ul1449 4ed.
Certification EAC
Fuses
Fuses type gG - 20A
Thermal disconnector Internal
Installation ground fault breaker Type 'S' or delayed