Contact : +33 1 41 23 50 23 (9:00 – 17:00 CEST)

Type 2 (or 3) AC surge protector - 3-phase+N

DS14-230/G
Part Number 471512
DS14-230/G
  • Type 2 (or 3) AC Multipolar surge protector
  • In : 5 kA
  • Imax total: 40 kA
  • Pluggable module by phase
  • Remote signaling option
  • EN 61643-11, IEC 61643-11, UL1449 ed.5 compliance

DS10 type2 AC surge protector are used mainly for primary protection of single and 3- phase networks at the main electrical panel. They provide common-mode or common and differential mode. This SPD is based on high energy varistor equipped with thermal disconnector and failure indicator, to comply with standards. The DS10 surge protectors are designed to be used in a multipolar configuration to protect single-phase, 3-phase or 3-phase+Neutral AC networks.They are sometimes associated with dedicated N/PE surge protector based on gas tube technology.

Select another reference:

SPD type
2 (or 3)
Network
230/400 V 3-phase+N
AC system
TT-TNS
Nominal line voltage
Un 230 Vac
Max. AC operating voltage
Uc 255 Vac
Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
UT 335 Vac withstand
Temporary Over Voltage (TOV) Characteristics - 120 mn
Without disconnection or with safety disconnection
UT 440 Vac disconnection
Temporary Over Voltage N/PE (TOV HT)
Without disconnection or with safety disconnection
UT 1200 V/300A/200 ms withstand
Residual Current
Leakage current to Ground
Ipe None
Operating current
Continious current at Uc
Ic 0.5 mA
Follow current
If None
Nominal discharge current
15 x 8/20 µs impulses
In 5 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 10 kA
Total Maximum discharge current
max. total withstand @ 8/20 µs
Imax Total 40 kA
Withstand on Combination waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
Uoc 10 kV
Withstand on overvoltages IEEE C62.41.1
10 kV
Connection mode(s)
L/N and N/PE
Protection mode(s)
Common/Differential mode
Protection level L/N
@ In (8/20µs)
Up L/N 0.9 kV
Protection level N/PE
@ In (8/20µs)
Up N/PE 1.5 kV
Admissible short-circuit current
Isccr 25 000 A
Technology
MOV+GDT
SPD configuration
3-phase+Neutral
Connection to Network
By screw terminals: 2.5-25mm² / by bus
Format
Plug-in modular box
Mounting
Symmetrical rail 35 mm (EN 60715)
Housing material
Thermoplastic UL94 V-0
Operating temperature
Tu -40/+85°C
Protection rating
IP20
Failsafe mode
Disconnection from AC network
Disconnection indicator
1 mechanical indicator by pole
Spare module(s)
DSM10-230 + DSM40G-600
Remote signaling of disconnection
option DS14S-230/G : output on changeover contact
Dimensions
See diagram
Standards compliance
IEC 61643-11 / EN 61643-11 / UL1449 ed.5
Certification
UL Recognized
Thermal disconnector
Internal
Installation ground fault breaker
Type 'S' or delayed
Back-up protection device
20 A min. - 125 A max. - Fuses type gG