Type 2 AC surge protector - 3-phase
DS72R-120/G
DS72R-120/G
Part Number: 491611
  • Re-inforced Type 2 AC surge protector
  • In : 30 kA
  • Imax : 70 kA
  • Pluggable module by phase
  • Remote signaling option
  • IEC 61643-11, EN 61643-11 compliance
  • UL1449 ed.4 approved
Installation Sheet

DS70R type 2 AC surge protector are used mainly for primary protection of single and three-phase networks at the main electrical panel. They provide common-mode protection and are available in one-phase, single-phase, 3-phase and 3-phase+Neutral. This SPD is based on association of high energy varistors equipped with thermal disconnector and failure indicator, to comply with standards.

The DS70R surge protectors are designed to be used in a multipolar configuration to protect single-phase, 3-phase or 3-phase+N AC networks. Each pole of the SPD is connected between Line(s) and PE and Neutral and PE.



SPD type
following IEC test
2
Network
120 V single-phase
AC system
TT
Nominal line voltage
120 Vac
Max. AC operating voltage L-N 150 Vac
Temporary Over Voltage (TOV) Charasteristics - 5 sec.
without disconnection
180 Vac withstand
Temporary Over Voltage (TOV) Charasteristics - 120 mn
without disconnection or with safety disconnection
230 Vac disconnection
Temporary Over Voltage N/PE (TOV HT)
without disconnection or with safety disconnection
1200 V/300A/200 ms withstand
Residual Current
Leakage current to Ground
None
Operating current
Continious current at Uc
< 1 mA
Follow current
None
Nominal discharge current
15 x 8/20 µs impulses
30 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
70 kA
Total Maximal discharge current
max. total withstand @ 8/20 µs
70 kA
Admissible short-circuit current 25000 A
Connection mode(s)
L/N and N/PE
Protection mode(s)
Common/Differential mode
Protection level L/N
@ In (8/20µs)
1 kV
Protection level N/PE
@ In (8/20µs)
1.5 kV
Residual voltage at 10 kA
@ 8/20µs
0.7 kV
Residuel voltage at 5 kA
@ 8/20µs
0.6 kV
 
Technology MOV
SPD configuration Single phase
Connection to Network By screw terminals: 2.5-25 mm² / by bus
Format Plug-in modular box
Mounting Symmetrical rail 35 mm (EN60715)
Housing material Thermoplastic UL94-V0
Operating temperature -40/+85°C
Protection rating IP20
Failsafe behavior Disconnection
Disconnection indicator 2 mechanical indicators by pole
Spare module(s)
DSM70R-120 + DSM70G-600
Remote signaling of disconnection option DS72RS-120/G : output on changeover contact
Dimensions
See diagram
Standards compliance IEC 61643-11 / EN 61643-11 / UL1449 4ed.
Certification EAC
Thermal disconnector Internal
Installation ground fault breaker Type 'S' or delayed
Fuses
Fuses Type gG - 100 A