Contact : +33 1 41 23 50 23 (9:00 – 17:00 CEST)

Type 2 AC surge protector - unipolar

DS71R-320
Part Number 321901
DS71R-320
  • Discover our latest innovation : the DAC80-10-320
  • Re-inforced Type 2 AC surge protector
  • In : 30 kA
  • Imax : 70 kA
  • Pluggable module by phase
  • IEC 61643-11, EN 61643-11 compliance

DS70R type 2 AC surge protector are used mainly for primary protection of single and three-phase networks at the main electrical panel. They provide common-mode protection and are available in one-phase, single-phase, 3-phase and 3-phase+Neutral. This SPD is based on association of high energy varistors equipped with thermal disconnector and failure indicator, to comply with standards. The DS70R surge protectors are designed to be used in a multipolar configuration to protect single-phase, 3-phase or 3-phase+N AC networks. Each pole of the SPD is connected between Line(s) and PE and Neutral and PE.

Select another reference:

SPD type
IEC 2
Network
230/400 V
Nominal line voltage
Un 230 Vac
Max. AC operating voltage
Uc 320 Vac
Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
UT 335 Vac withstand
Temporary Over Voltage (TOV) Characteristics - 120 mn
Without disconnection or with safety disconnection
UT 440 Vac disconnection
Residual Current
Leakage current to Ground
Ipe < 1 mA
Operating current
Continious current at Uc
Ic < 1 mA
Follow current
If None
Nominal discharge current
15 x 8/20 µs impulses
In 30 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 70 kA
Total Maximum discharge current
max. total withstand @ 8/20 µs
Imax Total 70 kA
Connection mode(s)
L/N or N/PE
Protection mode(s)
Common Mode or Differential Mode
Protection level
@ In (8/20µs)
Up 1.6 kV
Residual voltage at 5 kA
@ 5 kA (8/20µs)
Up-5kA 1 kV
Residual voltage at 10 kA
@ 8/20µs
Up-10kA 1.2 kV
Admissible short-circuit current
Isccr 25 000 A
Technology
MOV
SPD configuration
Single phase
Connection to Network
By screw terminals: 2.5-25mm² / by bus
Format
Plug-in modular box
Mounting
Symmetrical rail 35 mm (EN 60715)
Housing material
Thermoplastic UL94 V-0
Operating temperature
Tu -40/+85°C
Protection rating
IP20
Failsafe mode
Disconnection from AC network
Disconnection indicator
2 mechanical indicators by pole
Spare module(s)
DSM70R-320
Dimensions
See diagram
Weight
0.200 kg
Standards compliance
IEC 61643-11 / EN 61643-11 / UL1449 ed.5
Certification
UL Recognized
Thermal disconnector
Internal
Installation ground fault breaker
Type 'S' or delayed
Back-up protection device
100 A min. - 125 A max. - Fuses type gG