Compact 3-phase+N Type 2 surge protector - 120 V - Pluggable
DS440-120
DS440-120
Part Number: 311602
  • Compact 3-Phase Type 2 surge protector
  • In : 20 kA
  • Imax : 40 kA
  • Common mode
  • Pluggable module
  • Remode Signaling contact option
  • EN 61643-11, CEI 61643-11, UL1449 ed.4 compliance
Installation Sheet

The DS440 Type 2 surge protectors are compact devices designed to protect 3-phase+N networks at the main switchboard. They provide a common or common/differential mode protection.

This SPD is based on high energy varistor equipped with thermal disconnectors and failure indicator to comply with standards. The DS440 is DIN rail compatible and is built with a plug-in module and fixed base, which allows an easy and fast maintenance.



SPD type
following IEC test
2
Network
120/208 V 3-phase
AC system
TN
Nominal line voltage
120 Vac
Max. AC operating voltage L-N 150 Vac
Temporary Over Voltage (TOV) Charasteristics - 5 sec.
without disconnection
180 Vac withstand
Temporary Over Voltage (TOV) Charasteristics - 120 mn
without disconnection or with safety disconnection
230 Vac disconnection
Residual Current
Leakage current to Ground
< 0.5 mA
Follow current
None
Nominal discharge current
15 x 8/20 µs impulses
20 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
40 kA
Admissible short-circuit current 10000 A
Connection mode(s)
L/PE and N/PE
Protection mode(s)
Common mode
Protection level CM/DM
@ In (8/20µs)
0.9 kV
Residuel voltage at 5 kA
@ 8/20µs
0.6 kV
 
Technology MOV
SPD configuration 3-phase+Neutral
Connection to Network by screw terminals: 1.5-10mm² (L/N) or 2.5-25mm² (PE)
Format Plug-in modular box
Mounting Symmetrical rail 35 mm (EN60715)
Housing material Thermoplastic UL94-V0
Operating temperature -40/+85°C
Protection rating IP20
Failsafe behavior Disconnection
Disconnection indicator 4 mechanical indicators
Spare module(s)
DSM440-120
Remote signaling of disconnection Option DS440S-120 : output on changeover contact
Dimensions
See diagram
Certification EAC
Standards compliance IEC 61643-11 / EN 61643-11 / UL1449 4ed.
Fuses
Fuses type gG - 50 A
Thermal disconnector Internal
Installation ground fault breaker Type 'S' or delayed