Contact : +33 1 41 23 50 23 (9:00 – 17:00 CEST)

Type 2 AC surge protector - Single-phase

DS42S-480
Part Number 461015
DS42S-480
  • Discover our latest innovation : the DAC50S-20-530
  • Type 2 AC Multipolar surge protector
  • In: 20 kA
  • Imax total: 80 kA
  • Pluggable module for each phase
  • Remote signaling
  • EN 61643-11, IEC 61643-11, UL1449 ed.5

used mainly for primary protection of single and 4- phase networks at the main electrical panel. They provide common-mode or common and differential mode. This SPD is based on high energy varistor equipped with thermal disconnector and failure indicator, to comply with standards. The DS40 surge protectors are designed to be used in a multipolar configuration to protect single-phase, 3-phase or 3-phase+Neutral AC networks.They are sometimes associated with dedicated N/PE surge protector based on gas tube technology.

Select another reference:

Network
230-277 V Single-phase
AC system
IT
Nominal line voltage
Un 400 Vac
Max. AC operating voltage
Uc 440 Vac
Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
UT 700 Vac withstand
Temporary Over Voltage (TOV) Characteristics - 120 mn
Without disconnection or with safety disconnection
UT 920 Vac disconnection
Residual Current
Leakage current to Ground
Ipe < 1 mA
Operating current
Continious current at Uc
Ic 0.5 mA
Follow current
If None
Nominal discharge current
15 x 8/20 µs impulses
In 20 kA
Connection mode(s)
L/PE and N/PE
Protection mode(s)
Common mode
Protection level N/PE
@ In (8/20µs)
Up N/PE 2.5 kV
Protection level L/PE
@ In (8/20µs)
Up L/PE 2.5 kV
Admissible short-circuit current
Isccr 25 000 A
IP degree
IP 20
SPD configuration
Single phase
Format
Plug-in modular box
Operating temperature
Tu -40/+85°C
Failsafe mode
Disconnection from AC network
Disconnection indicator
1 mechanical indicator by pole
Spare module(s)
DSM40-480
Remote signaling of disconnection
Output on changeover contact
Weight
0.222 kg
Certification
CSA / UL Listed
Thermal disconnector
Internal
Installation ground fault breaker
Type 'S' or delayed
Back-up protection device
Fuses type gG - 50 A