Type 2 AC surge protector + RFI filtering
DS41HFS-230
Part Number 461590
- Type 2 AC surge protector
- RFI filtering integrated
- In : 20 kA
- Imax : 40 kA
- Pluggable module
- Remote signaling option
- EN 61643-11, IEC 61643-11, UL1449 ed.5 compliance
DS40HF Surge Protectors are designed for primary surge protection AC networks. They provide common-mode
protection (between the active conductors and ground).
A specific RFI filter is added in order to suppress high frequency disturtances.
The DS4xHF is DIN rail compatible and is built with a plug-in module and a fixed base, which allows a easy and fast maintenance.
Select another reference:
SPD type
|
IEC | 2 |
Network
|
230/400 V | |
Nominal line voltage
|
Un | 230 Vac |
Max. AC operating voltage
|
Uc | 255 Vac |
Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
|
UT | 335 Vac withstand |
Temporary Over Voltage (TOV) Characteristics - 120 mn
Without disconnection or with safety disconnection
|
UT | 440 Vac disconnection |
Operating current
Continious current at Uc
|
Ic | < 1 mA |
Follow current
|
If | None |
Nominal discharge current
15 x 8/20 µs impulses
|
In | 20 kA |
Max. discharge current
max. withstand @ 8/20 µs by pole
|
Imax | 40 kA |
RFI Filtering
|
0.1 - 30 MHz | |
Connection mode(s)
|
L/N or N/PE | |
Protection mode(s)
|
Common Mode or Differential Mode | |
Protection level
@ In (8/20µs)
|
Up | 1.25 kV |
Residual voltage at 5 kA
@ 5 kA (8/20µs)
|
Up-5kA | 1 kV |
Max. capacitance
|
C | 0,22 µF |
Admissible short-circuit current
|
Isccr | 25 000 A |
Technology
|
MOV+Filter | |
SPD configuration
|
Single phase | |
Connection to Network
|
By screw terminals: 2.5-25mm² | |
Format
|
Plug-in modular box | |
Mounting
|
Symmetrical rail 35 mm (EN 60715) | |
Housing material
|
Thermoplastic UL94 V-0 | |
Operating temperature
|
Tu | -40/+85°C |
Protection rating
|
IP20 | |
Failsafe mode
|
Disconnection from AC network | |
Disconnection indicator
|
1 mechanical indicator | |
Spare module(s)
|
DSM40HF-230 | |
Remote signaling of disconnection
|
Output on changeover contact | |
Dimensions
|
See diagram | |
Weight
|
0.103 kg |
Standards compliance
|
IEC 61643-11 / EN 61643-11 / UL1449 ed.5 | |
Certification
|
CSA |
Thermal disconnector
|
Internal | |
Installation ground fault breaker
|
Type 'S' or delayed | |
Back-up protection device
|
Fuses type gG - 50 A |