Type 2 AC surge protector - one-phase - pluggable
DAC50G-10-440
Part Number: 821120411
  • Type 2 AC surge protector
  • In : 20 kA
  • Imax : 50 kA
  • Pluggable module for each phase
  • Remote signaling option
  • NF EN 61643-11, IEC 61643-11 compliance
Installation Sheet

The pluggable surge protectors Type 2 DAC50, are designed to protect AC powerline at the main switchboard of the installation.

These SPDs are based on high energy varistor equipped with thermal disconnector and failure indicator, to comply with standards and to provide a maximum protection efficiency, an high impulse current capability and a improved reliability.

The surge protectors DAC50 are available in multipolar version and in several voltages to protect single or 3-phase networks.



SPD type
following IEC test
2
Max. AC operating voltage L-N 440 Vac
Temporary Over Voltage (TOV) Charasteristics - 5 sec.
without disconnection
580 Vac withstand
Temporary Over Voltage (TOV) Charasteristics - 120 mn
without disconnection or with safety disconnection
770 Vac disconnection
Residual Current
Leakage current to Ground
None
Follow current
Yes
Follow current interrupting capability
> 100 A
Nominal discharge current
15 x 8/20 µs impulses
20 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
50 kA
Admissible short-circuit current 50000 A
Protection level
@ In (8/20µs)
1.8 kV
Residual voltage at 10 kA
@ 8/20µs
1.5 kV
Residuel voltage at 5 kA
@ 8/20µs
1.3 kV
 
Technology GDT
SPD configuration 1-pole
Connection to Network By screw terminals: 2.5-25 mm² / by bus
Format Plug-in modular box
Mounting Symmetrical rail 35 mm (EN60715)
Housing material Thermoplastic UL94-V0
Operating temperature -40/+85°C
Protection rating IP20
Failsafe behavior Disconnection
Disconnection indicator 1 mechanical indicator
Spare module(s)
MDAC50G-440
Remote signaling of disconnection option DAC50GS-10-440 : output on changeover contact
Dimensions
See diagram
Certification OVE
Standards compliance IEC 61643-11 / EN 61643-11 / UL1449 4ed.
Fuses
Fuses Type gG - 125 A
Thermal disconnector Internal
Installation ground fault breaker Type 'S' or delayed