Contact : +33 1 41 23 50 23 (9:00 – 17:00 CEST)

Type 1+2 AC surge protector - 1-pole

DS250E-120
Part Number 3106
DS250E-120
  • Type 1 + 2 unipolar surge protector
  • Iimp: 25 kA on 10/350µs impulse
  • Imax: 140 kA on 8/20µs impulse
  • Internal disconnections, status indicators
  • Remote signaling
  • IEC 61643-11, EN 61643-11 and UL1449 ed.5 compliance

The DS250E is an extreme duty Type 1+2 designed to protect the entrance of the electrical installation. The DS250E is a one-pole SPD and can be used in common mode or common and differential mode. DS250E AC surge protectors are designed to be connected in multi-pole configuration to protect single-phase, 3-phase and 3-phase+neutral AC networks. This SPD is DIN rail compatible,

Select another reference:

SPD type
IEC 1+2
Network
120/208 V
Max. AC operating voltage
Uc 150 Vac
Max. load current
if series connection
IL 100 A
Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
UT 180 Vac withstand
Temporary Over Voltage (TOV) Characteristics - 120 mn
Without disconnection or with safety disconnection
UT 230 Vac disconnection
Residual Current
Leakage current to Ground
Ipe < 3 mA
Follow current
If None
Nominal discharge current
15 x 8/20 µs impulses
In 70 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 140 kA
Impulse current by pole
max. withstand 10/350µs by pole
Iimp 25 kA
Specific energy by pole
max. withstand 10/350 µs
W/R 156 kJ/ohm
Connection mode(s)
L/N or L/PE
Protection mode(s)
Common Mode or Differential Mode
Protection level
@ In (8/20µs)
Up 1 kV
Residual voltage at 5 kA
@ 5 kA (8/20µs)
Up-5kA 0.6 kV
Admissible short-circuit current
Isccr 50 000 A
Technology
MOV
SPD configuration
Single phase
Connection to Network
By screw terminals: 6-35mm² / by bus
Format
1-pole modular box
Mounting
Symmetrical rail 35 mm (EN 60715)
Housing material
Thermoplastic UL94 V-0
Operating temperature
Tu -40/+85°C
Protection rating
IP20
Failsafe mode
Disconnection from AC network
Disconnection indicator
3 mechanical indicators
Remote signaling of disconnection
Output on changeover contact
Dimensions
See diagram
Weight
0.23 kg
Standards compliance
IEC 61643-11 / EN 61643-11 / UL1449 ed.5
Certification
Thermal disconnector
Internal
Installation ground fault breaker
Type 'S' or delayed
Back-up protection device
Fuses type gG - 315 A