Type 1+2 AC surge protector
DS132R-400/G
Part Number 571422
- Type 1 + 2 AC multipolar surge protector
- In : 20 kA
- Iimp total : 50 kA
- Pluggable module for each phase
- Remote signaling
- EN 61643-11, IEC 61643-11 compliance
The DS130R is an extreme duty Type 1+2 designed to protect the entrance of the electrical installation.
The DS130R is a one-pole SPD and can be used in common mode or common and differential mode.
DS130R AC surge protectors are designed to be connected in multi-pole configuration to protect single-phase, 3-phase and 3-phase+neutral AC networks.
This SPD is DIN rail compatible.
Select another reference:
SPD type
|
IEC | 1+2 |
Network
|
230/400 V | |
AC system
|
IT | |
Nominal line voltage
|
Un | 400 Vac |
Max. AC operating voltage
|
Uc | 440 Vac |
Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
|
UT | 580 Vac withstand |
Temporary Over Voltage (TOV) Characteristics - 120 mn
Without disconnection or with safety disconnection
|
UT | 770 Vac disconnection |
Temporary Over Voltage N/PE (TOV HT)
Without disconnection or with safety disconnection
|
UT | 1200 V/300A/200 ms withstand |
Operating current
Continious current at Uc
|
Ic | < 1 mA |
Follow current
|
If | None |
Nominal discharge current
15 x 8/20 µs impulses
|
In | 20 kA |
Max. discharge current
max. withstand @ 8/20 µs by pole
|
Imax | 50 kA |
Impulse current by pole
max. withstand 10/350µs by pole
|
Iimp | 12.5 kA |
Total lightning current
max. total withstand @ 10/350µs
|
Itotal | 50 kA |
Withstand on overvoltages IEEE C62.41.1
|
20 kV | |
Specific energy by pole
max. withstand 10/350 µs
|
W/R | 40 kJ/ohm |
Connection mode(s)
|
L/N and N/PE | |
Protection mode(s)
|
Common/Differential mode | |
Protection level L/N
@ In (8/20µs)
|
Up L/N | 1.7 kV |
Protection level N/PE
@ In (8/20µs)
|
Up N/PE | 1.5 kV |
Admissible short-circuit current
|
Isccr | 25 000 A |
Technology
|
MOV | |
SPD configuration
|
3-phase+Neutral | |
Connection to Network
|
By screw terminals: 2.5-25mm² / by bus | |
Format
|
Plug-in modular box | |
Mounting
|
Symmetrical rail 35 mm (EN 60715) | |
Housing material
|
Thermoplastic UL94 V-0 | |
Operating temperature
|
Tu | -40/+85°C |
Protection rating
|
IP20 | |
Failsafe mode
|
Disconnection from AC network | |
Disconnection indicator
|
1 mechanical indicator by pole | |
Spare module(s)
|
DSM130R-400 + DSM130R-230/G | |
Remote signaling of disconnection
|
Output on changeover contact | |
Dimensions
|
See diagram |
Standards compliance
|
IEC 61643-11 / EN 61643-11 / UL1449 ed.5 | |
Certification
|
TUV |
Thermal disconnector
|
Internal | |
Installation ground fault breaker
|
Type 'S' or delayed | |
Back-up protection device
|
Fuses Type gG - 125 A |