Contact : +33 1 41 23 50 23 (9:00 – 17:00 CEST)

Type 1+2 AC surge protector single-phase

DS132R-280/G
Part Number 571122
DS132R-280/G
  • Discover our latest innovation : the DAC1-13-11-320
  • Type 1 + 2 AC multipolar surge protector
  • In : 20 kA
  • Iimp total : 25 kA
  • Pluggable module for each phase
  • Remote signaling (option)
  • EN 61643-11, IEC 61643-11 compliance

The DS130R is an extreme duty Type 1+2 designed to protect the entrance of the electrical installation. The DS130R is a one-pole SPD and can be used in common mode or common and differential mode. DS130R AC surge protectors are designed to be connected in multi-pole configuration to protect single-phase, 3-phase and 3-phase+neutral AC networks. This SPD is DIN rail compatible.

Select another reference:

SPD type
IEC 1+2
Network
230 V single-phase
AC system
TT-TN
Nominal line voltage
Un 230 Vac
Max. AC operating voltage
Uc 280 Vac
Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
UT 335 Vac withstand
Temporary Over Voltage (TOV) Characteristics - 120 mn
Without disconnection or with safety disconnection
UT 440 Vac disconnection
Temporary Over Voltage N/PE (TOV HT)
Without disconnection or with safety disconnection
UT 1200 V/300A/200 ms withstand
Operating current
Continious current at Uc
Ic None
Follow current
If None
Nominal discharge current
15 x 8/20 µs impulses
In 20 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 50 kA
Impulse current by pole
max. withstand 10/350µs by pole
Iimp 12.5 kA
Total lightning current
max. total withstand @ 10/350µs
Itotal 25 kA
Withstand on overvoltages IEEE C62.41.1
20 kV
Specific energy by pole
max. withstand 10/350 µs
W/R 40 kJ/ohm
Connection mode(s)
L/N and N/PE
Protection mode(s)
Common/Differential mode
Protection level L/N
@ In (8/20µs)
Up L/N 1.3 kV
Protection level N/PE
@ In (8/20µs)
Up N/PE 1.5 kV
Admissible short-circuit current
Isccr 25 000 A
Technology
MOV
SPD configuration
Single phase
Connection to Network
By screw terminals: 2.5-25mm² / by bus
Format
Plug-in modular box
Mounting
Symmetrical rail 35 mm (EN 60715)
Housing material
Thermoplastic UL94 V-0
Operating temperature
Tu -40/+85°C
Protection rating
IP20
Failsafe mode
Disconnection from AC network
Disconnection indicator
1 mechanical indicator by pole
Spare module(s)
DSM130R-280 + DSM130R-280/G
Remote signaling of disconnection
option DS132RS-280/G : output on changeover contact
Dimensions
See diagram
Standards compliance
IEC 61643-11 / EN 61643-11 / UL1449 ed.5
Certification
Thermal disconnector
Internal
Installation ground fault breaker
Type 'S' or delayed
Back-up protection device
Fuses Type gG - 125 A