Type 1+2 AC surge protector - 1-pole
DS250VG-690
DS250VG-690
Part Number: 63162
  • Type 1+2+3 surge protector
  • For 400/690 V network
  • In : 30 kA
  • Iimp : 25 kA
  • Low voltage Up
  • Internal disconnection, status indicator
  • Remote signaling
  • IEC 61643-11, EN 61643-11 and UL1449 ed3 compliance
Installation Sheet Range Technical Sheet

The DS250VG-690 AC surge protector is designed for 3-phase 690VAC and mainly use for wind generator networks,

Select another reference:

SPD type 1+2+3
Network 400/690 V
Nominal line voltage Un 690 Vac
Max. AC operating voltage L-N Uc 760 Vac
Max. load current IL 100 A
Temporary Over Voltage (TOV) Charasteristics - 5 sec. UT 1050 Vac withstand
Temporary Over Voltage (TOV) Charasteristics - 120 mn UT 1350 Vac withstand
Residual Current Ipe None
Follow current If None
Nominal discharge current In 30 kA
Max. discharge current Imax 100 kA
Impulse current by pole Iimp 25 kA
Withstand on Combination waveform IEC 61643-11 Uoc 6 kV
Withstand on overvoltages IEEE C62.41.1 20 kV
Specific energy by pole W/R 156 kJ/ohm
Connection mode(s) L/N or L/PE
Protection mode(s) Common Mode or Differential Mode
Protection level Up 4 kV
Admissible short-circuit current Isccr 50 000 A
Technology VG
SPD configuration 1-pole
Connection to Network By screw : 6-35 mm² (50mm² flexible)
Format 1-pole modular box
Mounting Symmetrical rail 35 mm (EN60715)
Housing material Thermoplastic UL94-V0
Operating temperature -40/+85°C
Protection rating IP20
Failsafe mode Disconnection
Disconnection indicator 1 mechanical indicator
Remote signaling of disconnection Output on changeover contact
Dimensions See diagram
Standards compliance IEC 61643-11 / EN 61643-11 / UL1449 4ed.
Certification EAC