Fuses+holders for protection of 3-phase+N Type 1 AC SPD

SFD1-13S-40
SFD1-13S-40
Part Number: 64053
  • Specific Fuses (SPD Fusing Disconnectors) for short circuit protection of AC SPD
  • For Type 1 SPD
  • Surge current withstand: 12.5 kA (@10/350µs)
  • Very compact
  • Fuses included
  • Remote signaling and status signaling

The SFD range has been especially designed to associated with Type 1 SPDs. These very specific fuses are able to conduct huge surge currents in rather small dimensions to protect Type 1 SPDs against harsh current circuit failures. In order to comply IEC 61643-11 standards, AC power SPD must be protected against short circuit failures: these specific fusing disconnectors must be installed in the SPD branch.


AC system IT
Max. AC operating voltage Uc 500 Vac
Nominal discharge current In 50 kA
Max. discharge current Imax 80 kA
Impulse current by pole Iimp 12.5 kA
Breaking capacity 100 000 A
Residual voltage Up < 0.4 kV @ 12.5 kA
Fuse configuration Cylindrical 14x51 mm
Fuse holder configuration Circuit breaker configuration for 3-phase+N
Mounting Symmetrical rail 35 mm (EN 60715)
Operating temperature Tu -40/+85°C
Protection rating IP20
Spare module(s) SFD1-13
Remote signaling of disconnection Yes
Dimensions See diagram
Standards compliance EN 61643-11 /IEC 61643-11 /EN 60269-1/EN 60269-2/IEC 60269-1/IEC 60269-2
Equivalent rated AC current 125 A